www.acehomeinspections.net

P.O. Box 1993
Alabaster, Alabama 35007
(205)401-3030

Customer
Sample

Home
Sample

Real Estate Agent
NONE - OWNER INSPECTION


Inspection Date 
Tuesday, June 14, 2005
Weather:
Clear and Sunny
Report ID:
01820
Temperature:
80 to 85 degrees
Inspected By 
Jeff Aiken

SUMMARY


www.acehomeinspections.net

P.O. Box 1993
Alabaster, Alabama 35007
(205)401-3030

Customer
Sample

Home
Sample

The following items or discoveries indicate that these systems or components do not function as intended or adversely affects the habitabilty of the dwelling; or appear to warrant further investigation by a specialist, or requires subsequent observation.

This summary shall not contain recommendations for routine upkeep of a system or component to keep it in proper functioning condition or recommendations to upgrade or enhance the function, efficiency, or safety of the home.

This Summary is not the entire report. The complete report may include additional information of concern to the customer. It is recommended that the customer read the complete report.

EXTERIOR DOORS, WINDOWS, SIDING, FOUNDATION, GUTTERS, ROOF, CHIMNEY
4.2 EXTERIOR DOORS, WINDOWS, SIDING, FOUNDATION, GUTTERS, ROOF, CHIMNEY
MISCELLANEOUS INFORMATION, (REFER TO REPORT PICTURES)
1-Recommend removal of all loose unused objects from the roof surface. There are three loose concrete blocks and an old refrigeration unit cover that should be removed.
4.3 EXTERIOR DOORS, WINDOWS, SIDING, FOUNDATION, GUTTERS, ROOF, CHIMNEY
MINOR REPAIRS, (REFER TO REPORT PICTURES)
1,2,3,4,5-There are several noticeable gaps between the front door and window framing and the brick veneer siding. These are located on both sides of the full length fixed side light windows beside the front entry doors and one side on each of the regular fixed windows beside the front entry doors. Immediate caulking is recommended in order to properly seal the building against any future moisture intrusion. The center metal plate piece between the two doors is loose and peeling off where water can enter behind it and cause deterioration. Immediate securing and caulking is recommended.
4.4 EXTERIOR DOORS, WINDOWS, SIDING, FOUNDATION, GUTTERS, ROOF, CHIMNEY
MINOR REPAIRS, (REFER TO REPORT PICTURES)
1,2,3-The front left corner of the flat roof parapet inner fiberglass asphalt shingle side has a large area of severe deterioration. This is allowing water to enter and drain down into the front office area corner closet, as shown. Immediate repairs are recommended by a licensed roof contractor.
4.5 EXTERIOR DOORS, WINDOWS, SIDING, FOUNDATION, GUTTERS, ROOF, CHIMNEY
MINOR REPAIRS, (REFER TO REPORT PICTURES)
1,2,3,4-View of flat style roof. Most flat roofs have a parapet. The outer side of the parapet from the top railing or parapet metal flashing or coping is covered with painted metal siding while the inner side is covered with fiberglass asphalt roof shingles. The parapet is a low wall along the perimeter where it modifies the wind flow over the roof so that the pressure on it is more uniformly distributed. It also provides a measure of safety in that no objects are so easily blown into the street below. Built-up roof systems are composed of three materials. They are bitumen, felts, and surfacing. Together they create a strong watertight membrane. A gravel stop around the perimeter along the parapet provides a finished edge for the built-up roofing, Not all built-up roofs have a top surface covered with aggregates. To maintain the weathering surface in reasonably good condition, the surface should be covered with a protective coating such as an asphalt based emulsion every three to six years. The rear section of the roof from the heating and air units back appears aged, weathered, and has a green growth over many areas. This green growth most likely has been caused from constant moisture around the heating and air units, and exhaust vents. Recommend a licensed roof contractor further investigate and remove green growth and possibly apply a protective roof coating as previously explained.
4.6 EXTERIOR DOORS, WINDOWS, SIDING, FOUNDATION, GUTTERS, ROOF, CHIMNEY
MINOR REPAIRS, (REFER TO REPORT PICTURES)
1,2,3,4,5,6,7,8-The entire roof is gently sloped down from the front to the rear to allow all water to drain to the rear and be carried away by the rear gutters. Apparently there are some low areas where water pools in the rear and does not properly run off. This pooling or standing water has caused the roof covering along the rear end to deteriorate over time and cause water to leak down into the interior attic. The ceiling tiles in this area are severely deteriorated and wet at the time of the inspection. The floor behind the cooler also has puddles of standing water. Some of this water may be condensation from the cooler. This goes hand-in-hand with the section 4.5 where a licensed roof contractor is recommended to make necessary repairs.

INTERIOR ROOMS
7.2 INTERIOR ROOMS
MINOR REPAIRS, (REFER TO REPORT PICTURES)
1-The fluorescent light in the water heater storage room flickers and does not fully light up. This most likely is a ballast issue.
7.3 INTERIOR ROOMS
MINOR REPAIRS, (REFER TO REPORT PICTURES)
1,2-There is one outlet and one light switch in the center hall time card room and one outlet in the rear right cooler room under the electrical panels that need proper covers. (safety issue)
7.4 INTERIOR ROOMS
MINOR REPAIRS, (REFER TO REPORT PICTURES)
1,2-The right water valve on the sink beside the rear metal door spins round and round and will not turn on. The large center stainless steel wash tub sink has a constant water drip.

ELECTRICAL (Service, Interior Distribution Panels, Exterior)
10.3 ELECTRICAL SYSTEM
MINOR REPAIRS, (REFER TO REPORT PICTURES)
1-One flood light in the front that overlooks the parking lot has broke off the mount and needs to be secured back in place.
10.4 ELECTRICAL SYSTEM
MINOR REPAIRS, (REFER TO REPORT PICTURES)
1,2-Two of the three exterior GFCI type 120 volt receptacle weather covers are broken off and need to be replaced.
10.5 ELECTRICAL SYSTEM
MINOR REPAIRS, (REFER TO REPORT PICTURES)
1,2,3-The 240 volt sub-panel located beside the two 120 volt panels was blocked by a large cabinet and an in-use soft ice cream machine, so the interior of this panel was not inspected. Portions of the front cover are loose and are being held on with duct tape. The left side of the cover can be easily moved in and out and needs to be properly secured to the panel. One panel filler plate is missing, leaving the interior of the panel exposed. This is a potential high voltage safety issue that needs immediate attention. Recommend licensed electrical contractor install a filler plate and secure cover to panel.(safety issue)

COOLING SYSTEM
12.1 COOLING SYSTEM
MINOR REPAIRS, (REFER TO REPORT PICTURES)
1-The cooling unit located on the roof for the left side of the building has a 14 degree temperature differential from the return and supply vents. This is within the normal range of 14 to 22 degrees. The cooling unit for the right side of the building only had a 5 degree temperature differential then stopped working altogether. A licensed heating and air contractor was working on the units at the time of the inspection.

Left side unit: 48TFE is a 1-piece gas heating, electric cooling unit Single-Package STANDARD EFFICIENCY Roof Unit. It has a fully insulated cabinet, belt-drive evaporator fan motor, 2-inch disposable return air filter, and solid state heating controls with diagnostics. It uses R22 freon. (12.5 ton unit)

Right side unit: 48TME is a 1-piece gas heating, electric cooling unit Single-Package HIGH EFFICIENCY Roof Unit. It has a fully insulated cabinet, belt-drive evaporator fan motor, 2-inch disposable return air filter, and solid state heating controls with diagnostics. It uses R22 freon. (8.5 ton unit)

www.acehomeinspections.net

Home inspectors are not required to report on the following: Life expectancy of any component or system; The causes of the need for a repair; The methods, materials, and costs of corrections; The suitability of the property for any specialized use; Compliance or non-compliance with codes, ordinances, statutes, regulatory requirements or restrictions; The market value of the property or its marketability; The advisability or inadvisability of purchase of the property; Any component or system that was not observed; The presence or absence of pests such as wood damaging organisms, rodents, or insects; or Cosmetic items, underground items, or items not permanently installed. Home inspectors are not required to: Offer warranties or guarantees of any kind; Calculate the strength, adequacy, or efficiency of any system or component; Enter any area or perform any procedure that may damage the property or its components or be dangerous to the home inspector or other persons; Operate any system or component that is shut down or otherwise inoperable; Operate any system or component that does not respond to normal operating controls; Disturb insulation, move personal items, panels, furniture, equipment, plant life, soil, snow, ice, or debris that obstructs access or visibility; Determine the presence or absence of any suspected adverse environmental condition or hazardous substance, including but not limited to mold, toxins, carcinogens, noise, contaminants in the building or in soil, water, and air; Determine the effectiveness of any system installed to control or remove suspected hazardous substances; Predict future condition, including but not limited to failure of components; Since this report is provided for the specific benefit of the customer(s), secondary readers of this information should hire a licensed inspector to perform an inspection to meet their specific needs and to obtain current information concerning this property.

www.acehomeinspections.net

Prepared Using HomeGauge http://www.homegauge.com/ SHGI (c) 2000-2003 : Licensed To Jeffrey James Aiken

 

GARAGES, CARPORTS, DRIVE-THRUS

Styles & Materials
DRIVE-THRUS:
REAR COVERED DRIVE-THRU
ROOF INFO:
SLOPED OFF BUILDING
METAL SHEETING ROOF COVERING
STRUCTURE:
2 BRICK COLUMNS
VINYL COVERED CEILING



Inspection Items
1.0 GARAGES, CARPORTS, DRIVE-THRUS
Picture 1
Picture 2
Comments: FOR YOUR INFORMATION
1,2-The exterior drive-thru brick columns and roof construction appeared adequate. The roof covering is caulked where it attaches to the main building and the brick columns were free of cracks and deterioration. this is good!
1.1 EXTERIOR: ROOF, EAVES, GUTTERS, WALLS, SIDING, WINDOWS, DOORS, FOUNDATION, LANDSCAPING (Visible condition.)
Comments: INSPECTED

WALKWAYS, DRIVEWAYS, LANDSCAPING, RETAINING WALLS

Styles & Materials
WALKWAYS:
CONCRETE
DRIVEWAYS:
ASPHALT
LANDSCAPING:
SLOPED DOWN LEFT TO RIGHT
LANDSCAPING:
RELATIVELY LEVEL PROPERTY
LANDSCAPING:
TALL TREES IN FAR REAR



Inspection Items
2.0 WALKWAYS, DRIVEWAYS, LANDSCAPING, RETAINING WALLS
Comments: MISCELLANEOUS INFORMATION
1-The asphalt parking and driveways appeared to be overall adequate and free of major holes, however some areas are cracked and deteriorated. Recommend all areas be repaired. (Maintenance tip.)
2.1 WALKWAYS, DRIVEWAYS, PATIOS, LANDSCAPING, RETAINING WALLS (Visible condition. Checking for proper water runoff away from the house, the landscape for presence of holes, sunken areas, bald spots, eroding areas, and tripping hazards, trees and vegetation clearances, and drainage weep holes or drains at the base of retaining walls.)
Comments: INSPECTED

PORCHES, DECKS, PATIOS, STEPS, STAIRS, RAILINGS, BANISTERS

Styles & Materials
PATIOS:
FRONT OPEN PATIO
PATIO FOUNDATION:
CONCRETE SLAB
PATIO INFO:
CONCRETE TABLES AND BENCHES
STEPS:
NONE
STAIRWAYS:
NONE
RAMPS:
RIGHT SIDE ENTRY DOOR
RAILINGS AND BANISTERS:
RIGHT SIDE STEEL TUBE RAILING



Inspection Items
3.0 PORCHES, DECKS, PATIOS, STEPS, STAIRS, RAMPS, RAILINGS, BANISTERS
Comments: FOR YOUR INFORMATION
1-The right side wheelchair ramp and steel hand-rail appeared adequate and robust. This is good!
3.1 PORCH ROOF, EAVES, GUTTERS, ATTIC, VENTILATION, COLUMNS, FOUNDATION, FLOOR, COVERINGS, STORAGE CLOSETS (Visible condition.)
Comments: INSPECTED
3.2 LIGHTS, SWITCHES, OUTLETS AND EXPOSED WIRING (Visible condition and operation.)
Comments: INSPECTED
3.3 STORAGE CLOSET DOORS, LIGHTS, SWITCHES, OUTLETS (Visible condition and operation.)
Comments: INSPECTED
3.4 STOOPS, STEPS, STAIRS, BANISTERS, AND RAILINGS (Visible condition. Checking for potential tripping hazards from variations in step riser heights, narrow tread steps, unlevel steps or steep stairs. Checking for adequate headroom.)
Comments: INSPECTED

EXTERIOR DOORS, WINDOWS, SIDING, FOUNDATION, GUTTERS, ROOF, CHIMNEY

Styles & Materials
EXTERIOR DOORS:
FRONT ENTRY DOORS
RIGHT SIDE ENTRY DOORS
LEFT SIDE ENTRY DOOR
REAR ENTRY DOOR
EXTERIOR DOORS:
FRONT METAL FULL GLASS
RIGHT SIDE METAL FULL GLASS
LEFT SIDE METAL DOOR
REAR METAL DOOR
EXTERIOR DOORS:
DEADBOLTS
FRONT OUTER/INNER ENTRY
RIGHT OUTER/INNER ENTRY
INTERIOR DOORS:
WOOD/HOLLOW/FLUSH
BUILDING WINDOWS:
METAL FRAME
BUILDING WINDOW TYPE:
FIXED
BUILDING WINDOW TYPE:
DOUBLE PANE
SIDING MATERIAL:
BRICK
SIDING STYLE:
BRICK
GUTTER MATERIAL:
ALUMINUM
FOUNDATION MATERIAL:
POURED CONCRETE
SOFFIT/FASCIA MATERIAL:
VINYL AND ALUMINUM
VIEWED ROOF FROM:
WALK ENTIRE ROOF/USE LADDER
ROOF TYPE:
FLAT
ROOF COVERING:
TAR AND GRAVEL
ESTIMATED ROOF AGE:
ORIGINAL
ROOF PENETRATIONS:
6 TOTAL ROOF PENETRATIONS
2 HEAT AND AIR UNITS
1 VENT SYSTEM
2 REFRIGERATION CONDENSERS
1 FLUE VENT



Inspection Items
4.0 EXTERIOR DOORS, WINDOWS, SIDING, FOUNDATION, GUTTERS, ROOF, CHIMNEY
Picture 1
Picture 2
Picture 3
Picture 4
Picture 5
Comments: FOR YOUR INFORMATION
1,2,3,4,5-The building exterior siding is brick, with metal windows and framing, metal entry doors and framing, and vinyl and aluminum covered soffit and fascia, making the building very low maintenance. This is good!!!!!
4.1 EXTERIOR DOORS, WINDOWS, SIDING, FOUNDATION, GUTTERS, ROOF, CHIMNEY
Picture 1
Picture 2
Comments: MISCELLANEOUS INFORMATION
1-The left side exterior metal door needs to be painted. (Maintenance tip.)

2-The interior side of the rear metal door frame is slightly corroded along the bottom edges. Patching and painting is recommended. (Maintenance tip.)
4.2 EXTERIOR DOORS, WINDOWS, SIDING, FOUNDATION, GUTTERS, ROOF, CHIMNEY
Comments: MISCELLANEOUS INFORMATION, (REFER TO REPORT PICTURES)
1-Recommend removal of all loose unused objects from the roof surface. There are three loose concrete blocks and an old refrigeration unit cover that should be removed.
4.3 EXTERIOR DOORS, WINDOWS, SIDING, FOUNDATION, GUTTERS, ROOF, CHIMNEY
Picture 1
Picture 2
Picture 3
Picture 4
Picture 5
Comments: MINOR REPAIRS, (REFER TO REPORT PICTURES)
1,2,3,4,5-There are several noticeable gaps between the front door and window framing and the brick veneer siding. These are located on both sides of the full length fixed side light windows beside the front entry doors and one side on each of the regular fixed windows beside the front entry doors. Immediate caulking is recommended in order to properly seal the building against any future moisture intrusion. The center metal plate piece between the two doors is loose and peeling off where water can enter behind it and cause deterioration. Immediate securing and caulking is recommended.
4.4 EXTERIOR DOORS, WINDOWS, SIDING, FOUNDATION, GUTTERS, ROOF, CHIMNEY
Picture 1
Picture 2
Picture 3
Comments: MINOR REPAIRS, (REFER TO REPORT PICTURES)
1,2,3-The front left corner of the flat roof parapet inner fiberglass asphalt shingle side has a large area of severe deterioration. This is allowing water to enter and drain down into the front office area corner closet, as shown. Immediate repairs are recommended by a licensed roof contractor.
4.5 EXTERIOR DOORS, WINDOWS, SIDING, FOUNDATION, GUTTERS, ROOF, CHIMNEY
Picture 1
Picture 2
Picture 3
Picture 4
Comments: MINOR REPAIRS, (REFER TO REPORT PICTURES)
1,2,3,4-View of flat style roof. Most flat roofs have a parapet. The outer side of the parapet from the top railing or parapet metal flashing or coping is covered with painted metal siding while the inner side is covered with fiberglass asphalt roof shingles. The parapet is a low wall along the perimeter where it modifies the wind flow over the roof so that the pressure on it is more uniformly distributed. It also provides a measure of safety in that no objects are so easily blown into the street below. Built-up roof systems are composed of three materials. They are bitumen, felts, and surfacing. Together they create a strong watertight membrane. A gravel stop around the perimeter along the parapet provides a finished edge for the built-up roofing, Not all built-up roofs have a top surface covered with aggregates. To maintain the weathering surface in reasonably good condition, the surface should be covered with a protective coating such as an asphalt based emulsion every three to six years. The rear section of the roof from the heating and air units back appears aged, weathered, and has a green growth over many areas. This green growth most likely has been caused from constant moisture around the heating and air units, and exhaust vents. Recommend a licensed roof contractor further investigate and remove green growth and possibly apply a protective roof coating as previously explained.
4.6 EXTERIOR DOORS, WINDOWS, SIDING, FOUNDATION, GUTTERS, ROOF, CHIMNEY
Picture 1
Picture 2
Picture 3
Picture 4
Picture 5
Picture 6
Picture 7
Picture 8
Comments: MINOR REPAIRS, (REFER TO REPORT PICTURES)
1,2,3,4,5,6,7,8-The entire roof is gently sloped down from the front to the rear to allow all water to drain to the rear and be carried away by the rear gutters. Apparently there are some low areas where water pools in the rear and does not properly run off. This pooling or standing water has caused the roof covering along the rear end to deteriorate over time and cause water to leak down into the interior attic. The ceiling tiles in this area are severely deteriorated and wet at the time of the inspection. The floor behind the cooler also has puddles of standing water. Some of this water may be condensation from the cooler. This goes hand-in-hand with the section 4.5 where a licensed roof contractor is recommended to make necessary repairs.
4.7 WINDOWS, SHUTTERS AND AWNINGS (Visible condition and checking for the presence and functionality of window flashing and operation of windows and window locks.)
Comments: INSPECTED
4.8 ENTRY DOORS, STORM DOORS, SECURITY DOORS, AND DOORBELL (Visible condition and operation, checking hardware, locks, coverings, frame, trim, weatherstripping, presence of deadbolts on all exterior doors, proper locking, opening, and closing of sliding glass doors, and the presence of a security dead-pin in all sliding glass doors.)
Comments: INSPECTED
4.9 FOUNDATION WALLS AND MORTAR JOINTS (Visible condition, checking for cracked, crumbled, loose, missing, eroded areas, or large gaps)
Comments: INSPECTED
4.10 EXTERIOR WALL COVERINGS, FLASHING,TRIM, AND CAULKING (Visible condition. A wall flashing is defined as a material used around angles or junctions on exterior walls to prevent water leakage.)
Comments: INSPECTED
4.11 HOUSE FRAMING (Visible condition, checking for any cracks developing outside of the house, cracks between a chimney and the exterior wall or any cracks running outward at an angle from the upper corners of windows and door frames.)
Comments: INSPECTED
4.12 OUTSIDE ACCESS TO HOUSE IS RODENT PROOF
Comments: INSPECTED
4.13 ROOF COVERING (Visible condition. Checking roof penetrations such as, roof vents, ridge vents, wind turbines, soffit vents, gable vents, chimneys, furnace flues, water heater flues, plumbing vents, skylights and any other penetrations. Checking flashings which are used to seal around roof penetrations and intersections. Checking rain caps on chimneys and flues.)
Comments: INSPECTED
4.14 SOFFIT, FASCIA, EAVES, GUTTERS, DOWNSPOUTS (Visible condition. Checking if gutters are provided where necessary, including porches, flat roofs, and dormers. Checking whether splasblocks are in place if underground piping is not used for rain gutter drainage.)
Comments: INSPECTED

ATTIC, ROOF INTERIOR

Styles & Materials
ROOF STRUCTURE:
2x4 WOOD RAFTERS
PLYWOOD ROOF DECKING
CEILING STRUCTURE:
2X4 WOOD CEILING JOISTS
TRUSS STYLE 2 FT AIR GAP
BETWEEN CEILING TILES AND ROOF
INSULATION TYPE:
BATT
FIBERGLASS
INSULATION INCHES:
6 INCHES
R- VALUE:
R-19
ACCESS LOCATED IN:
RAISING CEILING TILES



Inspection Items
5.0 ATTIC, ROOF INTERIOR
Comments: FOR YOUR INFORMATION
1-Adequate fiberglass batt insulation was observed on top of the suspended ceiling tiles and the recessed ceiling lights are not covered with insulation. This is good!
5.1 ATTIC, ROOF INTERIOR
Picture 1
Picture 2
Picture 3
Picture 4
Comments: MISCELLANEOUS INFORMATION
1,2,3,4-The majority of wood members throughout the attic and around roof penetrations were relatively free of visible moisture discoloration and deterioration. The roof decking around some penetrations has some slight discoloration that was poked and found to still be structurally adequate. There were two areas of major deterioration. See sections 4.4, 4.5, and 4.6 for further information regarding attic wood member discoloration and deterioration.
5.2 ATTIC, ROOF INTERIOR (Visible condition. Checking attic insulation, exposed wiring, lights and water pipes. Checking to see that all attic areas are accessible, all exposed sections of chimney in attic are free of soot and creosote leakage, that soffit vents are not covered with insulation, and attic ventilation vent screening which keeps animals out)
Comments: INSPECTED
5.3 GAS FLUE AND CHIMNEY FIRESTOPPING (Visible condition. Firestopping refers to size of the hole made in the ceiling and roof so as to maintain the proper clearance from a hot metal flue pipe or chimney brick.)
Comments: INSPECTED
5.4 DO ALL FLUES AND VENTS PRESENT IN ATTIC TERMINATE TO THE EXTERIOR (Water heater flue, furnace flue, metal chimney flue, plumbing vents, bathroom fan vents, range hood vent, dryer vent, etc...)
Comments: INSPECTED
5.5 RAFTERS, DECKING, JOISTS OR TRUSSES (Visible condition. Check for rafters pulling away from ridge board, rot, cracks, splits, cut, altered or missing supports.)
Comments: INSPECTED
5.6 IS ATTIC FREE OF VISIBLE ROOF LEAKS OR DETERIORATION (Flashing refers to materials, usually metal, that join parts of the house to the roof. Common places where roof leaks occur are flashings around chimneys, metal gas flues, plumbing vents, turbines, dormers, valleys, or any other roof penetrations or intersections.)
Comments: INSPECTED
5.7 IS ATTIC FREE OF VISIBLE CONDENSATION OR MOISTURE DAMAGE DUE TO IMPROPER VENTILATION (Often what appears to be a leak is in fact condensation, and a sign of inadequate ventilation. Proper attic ventilation reduces heat in summer and prevents condensation in winter. It allows air to carry off water vapor before it can condense and cause moisture damage.)
Comments: INSPECTED
5.8 INSTALLED MECHANICAL VENTILATION SYSTEMS (Visible condition and operation of power ventilators and fans)
Comments: INSPECTED

KITCHEN, APPLIANCES

Styles & Materials



Inspection Items
6.0 KITCHEN
Comments: FOR YOUR INFORMATION

INTERIOR ROOMS

Styles & Materials
CEILING MATERIAL:
SUSPENDED CEILING TILES
WALL MATERIAL:
PLASTERBOARD
VINYL WALL SHEETING
WALLPAPER / CHAIR-RAIL
FLOOR MATERIAL:
CARPET
CERAMIC TILE
INTERIOR ROOMS:
CAKE ROOM
WATER HEATER STORAGE ROOM
TIME CARD ROOM
INTERIOR ROOMS:
FRONT OFFICE
LEFT SIDE FREEZER/SINK ROOM
LEFT SIDE KITCHEN ROOM
INTERIOR ROOMS:
RIGHT SIDE CUSTOMER ROOM
CENTER CUSTOMER ROOM
INTERIOR ROOM INFO:
CAKE ROOM SMALL SINK
CUSTOMER ROOM BOOTHS/TABLES
INTERIOR ROOM INFO:
FRONT OFFICE STORAGE CLOSET
CEILING FANS:
5 IN CUSTOMER ROOM



Inspection Items
7.0 INTERIOR ROOMS
Picture 1
Picture 2
Comments: MISCELLANEOUS INFORMATION
1,2-The majority of all interior wall coverings and tables were adequate and free of deterioration, however some seats have some slits and the wallpaper has some minor tears. (cosmetic issues)
7.1 INTERIOR ROOMS
Picture 1
Picture 2
Picture 3
Picture 4
Comments: MISCELLANEOUS INFORMATION
1,2,3,4-The underside and piping under the large stainless steel washtub style sinks in the left side refrigeration room appear aged, but adequate and not leaking at the time of inspection. There is one plumbing fixture that has been previously removed where the drain piping still exists.
7.2 INTERIOR ROOMS
Comments: MINOR REPAIRS, (REFER TO REPORT PICTURES)
1-The fluorescent light in the water heater storage room flickers and does not fully light up. This most likely is a ballast issue.
7.3 INTERIOR ROOMS
Picture 1
Picture 2
Picture 3
Comments: MINOR REPAIRS, (REFER TO REPORT PICTURES)
1,2-There is one outlet and one light switch in the center hall time card room and one outlet in the rear right cooler room under the electrical panels that need proper covers. (safety issue)
7.4 INTERIOR ROOMS
Picture 1
Picture 2
Comments: MINOR REPAIRS, (REFER TO REPORT PICTURES)
1,2-The right water valve on the sink beside the rear metal door spins round and round and will not turn on. The large center stainless steel wash tub sink has a constant water drip.
7.5 CEILING AND WALLS (Visible condition.)
Comments: INSPECTED
7.6 WINDOWS, DOORS, FLOOR, LIGHTS, SWITCHES, OUTLETS (Visible condition and operation.)
Comments: INSPECTED

BATHROOMS

Styles & Materials
DRAIN PIPING UNDER SINKS:
WHITE PVC(polyvinyl chloride) PIPING
SINK WATER SUPPLY CONNECTION:
GRAY PLASTIC TUBING
BATHROOMS:
1 MENS ROOM
1 LADIES ROOM
BATHROOM CEILING:
PLASTERBOARD
BATHROOM WALLS:
PLASTERBOARD
BATHROOM FLOORS:
CERAMIC TILE
SINKS AND VANITIES:
1 CULTERED MARBLE WITH VANITY
1 WALL SINK
BATHROOM INFO:
1 MENS COMMODE
1 MENS URINAL
BATHROOM INFO:
1 LADIES COMMODE
WORLD HAND DRYERS



Inspection Items
8.0 BATHROOM
Picture 1
Picture 2
Comments: FOR YOUR INFORMATION
1,2-Restroom piping appeared adequate and robust, as shown. Both sinks were filled and allowed to drain. No water leakage was observed. This is good!
8.1 BATHROOM (Visible condition of ceiling, walls, cabinets, countertops, and caulking.)
Comments: INSPECTED
8.2 BATHROOM (Visible condition and operation of windows, doors, floor, cabinet doors, drawers, exhaust fans, lights, switches, outlets, sinks, tubs, showers, and commodes. Checking presence of cut-off valves for faucets and commodes, proper draining of sinks, tubs, showers and commodes, use of P-traps and not old S-traps, proper air-gap for sinks, tubs, and hand-held shower wands to prevent back siphonage, faucets for improper hammering and vibrating noises when turned on/off rapidly, adequacy of hot and cold water pressure, volume, and temperature, exhaust fans for proper venting to building exterior and outlet GFCI protection.)
Comments: INSPECTED

PLUMBING (Main, Exterior, Water Heater, Washer, Dryer)

Styles & Materials
PLUMBING SUPPLY:
COPPER
DISTRIBUTION:
COPPER
PLUMBING WASTE:
PVC
WASTE SYSTEM:
UNKNOWN
WATER SOURCE:
PUBLIC
WATER CUT-OFF:
AT STREET
WATER HEATER DATE:
12/1986
WATER HEATER POWER SOURCE:
NATURAL GAS
WATER HEATER LOCATION:
INSIDE STORAGE ROOM
CAPACITY:
50 GALLONS
MANUFACTURER:
RUUD



Inspection Items
9.0 PLUMBING SYSTEM
Picture 1
Picture 2
Picture 3
Comments: FOR YOUR INFORMATION
1,2,3-The water heater burner compartment appeared clean. Burner flame characteristics are normal, as shown, indicating proper combustion. Water heater is almost 18 years years old and nearing the end of its useful life which is normally 15 to 20 years. It may last several more years or could quit working and need replaced tomorrow. The unit was fully functional at the time of inspection and metal flue firestopping appeared adequate. This is good!
9.1 PLUMBING SYSTEM
Comments: FOR YOUR INFORMATION
1-Commercial fryer gas piping appeared adequate.
9.2 PLUMBING SYSTEM
Picture 1
Picture 2
Picture 3
Comments: MISCELLANEOUS INFORMATION
1,2,3-----UPGRADE-----The simplest backflow protection is the simple air gap between the end of a sink faucet where the water exits and the flood rim of the sink as explained in the bathroom section. Another place where backflow protection is needed is on outside hose bibs or faucets. This involves purchasing a relatively inexpensive backflow preventer that easily screws on to the end of the faucet that will allow water to flow in only one direction, out of your faucet. This prevents any contaminated water in your hose from being sucked back through the house water supply. It is recommended that present hose bibs be upgraded with backflow preventers. A proper example of a backflow preventer is shown in photo 2.
9.3 WATER HEATER, PTV - PRESSURE TEMPERATURE VALVE, PTV DRAIN PIPING (Visible condition. Checking presence of a drain pan under unit if installed in attic or room over a living area, and presence of a cold water inlet water cut-off valve.)
Comments: INSPECTED
9.4 FLUE PIPE AND VENTING (Visible condition checking pipe rise, diameter, junction fit, screws, and clearances. A properly vented gas system exhausts combustion products to exterior and provides adequate oxygen for combustion.)
Comments: INSPECTED
9.5 COMBUSTION AIR SUPPLY (Combustion is a chemical reaction that occurs when fuel gases combine with oxygen and ignite. Visual inspection of flame characteristics is a good indicator of air/gas mixture problems that cause incomplete combustion.)
Comments: INSPECTED
9.6 IF FLUE PIPE GOES TO FURNACE FLUE, IS IT ON TOP (If both the water heater and furnace go into the same chimney sleeve, then the furnace must be on the bottom because it has most BTU's and makes the draft.)
Comments: INSPECTED
9.7 WAS GAS WATER HEATER AREA CHECKED WITH SNIFFER AND FOUND FREE OF LEAKS
Comments: INSPECTED
9.8 EXPOSED INTERIOR WATER PIPING (Visible condition, looking for leaks, corrosion, sagging sections, and valves where it enters house and stops at the point where it enters rooms where it then will be described in each rooms description in this report.)
Comments: INSPECTED
9.9 EXTERIOR HOSE FAUCETS, WATER PRESSURE, WATER VOLUME, WATER DRAINS (Visible condition and operation. Checking for presence of faucet backflow preventers.)
Comments: INSPECTED

ELECTRICAL (Service, Interior Distribution Panels, Exterior)

Styles & Materials
SERVICE DROP TO HOUSE:
BELOW GROUND
SERVICE DROP TO HOUSE:
IN CONDUIT
SERVICE DROP TO HOUSE:
ALUMINUM
MAIN POWER DISCONNECT:
RATED 225 AMP
MAIN POWER DISCONNECT:
IN MAIN PANEL
MAIN PANEL CAPACITY:
225 AMPS
MAIN PANEL TYPE:
CIRCUIT BREAKERS
MAIN PANEL LOCATION:
LEFT SIDE FREEZER ROOM
BREAKERS:
SQUARE D
MAIN PANEL MANUFACTURER:
SQUARE D
MAIN PANEL MANUFACTURED:
UNKNOWN
WIRING METHODS:
ROMEX
15 AND 20 AMP CIRCUIT TYPE:
ALL COPPER
MAIN PANEL INFO:
240 VOLT
FREEZERS
DEEP FRYERS
SUB-PANEL A CAPACITY:
200 AMP
SUB-PANEL A TYPE:
CIRCUIT BREAKERS
SUB-PANEL A MANUFACTURER:
SQUARE D
SUB-PANEL A LOCATION:
LEFT SIDE FREEZER ROOM
BREAKERS:
SQUARE D
200 AMP MAIN BREAKER
15 AND 20 AMP CIRCUIT TYPE:
ALL COPPER
SUB-PANEL A INFO:
LIGHTS AND OUTLETS
MISC 120 VOLTS
SUB-PANEL B CAPACITY:
200 AMP
SUB-PANEL B TYPE:
CIRCUIT BREAKERS
SUB-PANEL B MANUFACTURER:
SQUARE D
SUB-PANEL B LOCATION:
LEFT SIDE FREEZER ROOM
BREAKERS:
SQUARE D
200 AMP MAIN BREAKER
15 AND 20 AMP CIRCUIT TYPE:
ALL COPPER
SUB-PANEL B INFO:
LIGHTS AND OUTLETS
MISC 120 VOLTS
EXTERIOR OUTLETS:
3 TOTAL



Inspection Items
10.0 ELECTRICAL SYSTEM
Picture 1
Picture 2
Comments: FOR YOUR INFORMATION
1,2-The electrical system is grounded properly to an exterior ground rod. This is good!
10.1 ELECTRICAL SYSTEM
Picture 1
Picture 2
Picture 3
Comments: FOR YOUR INFORMATION
1,2,3-The two electrical sub-panels inspected appeared adequate and free of deterioration and corrosion. This is good!
10.2 ELECTRICAL SYSTEM
Picture 1
Picture 2
Comments: MISCELLANEOUS INFORMATION
1,2-----UPGRADE-----All 120 volt outlets checked were properly grounded. This is good! It is always recommended, but not required, based on the age of the building, that all outlets within six feet of a sink be upgraded to GFCI type outlets. Please read general GFCI information below and see remainder of electrical section for all items inspected. The only GFCI outlets observed were along the exterior of the building.

GENERAL GFCI AND AFCI INFORMATION:

A GFCI or Ground-Fault-Circuit Interrupter is a device intended for the protection of personnel that functions to de-energize a circuit within an established period of time when a current to ground exceeds the values established for a Class A device. Class A ground-fault circuit interrupters trip when the current to ground has a value in the range of 4ma (milli-amps) to 6ma (milli-amps).

Starting January 1, 2002, The National Electrical Code, Section 210-12, requires that all branch circuits supplying 125 volts, single phase, 15 and 20 ampere outlets installed in bedrooms be protected by an arc-fault circuit interrupter. They may eventually be required elsewhere, but for now just in bedrooms because a CPSC study showed many home fire deaths were related to bedroom circuits. The AFCI - arc-fault-circuit-interrupter will shut off a circuit in a fraction of a second if arcing develops. The current inside of an arc is not always high enough to trip a regular breaker.

There is a difference between AFCIs and GFCIs. AFCIs are intended to reduce the likelihood of fire caused by electrical arcing faults: whereas, GFCIs are personnel protection intended to reduce the likelihood of electric shock hazard.

AFCI's in the bedrooms are always recommended, but are not required because the house was built before 2002.
10.3 ELECTRICAL SYSTEM
Comments: MINOR REPAIRS, (REFER TO REPORT PICTURES)
1-One flood light in the front that overlooks the parking lot has broke off the mount and needs to be secured back in place.
10.4 ELECTRICAL SYSTEM
Picture 1
Picture 2
Comments: MINOR REPAIRS, (REFER TO REPORT PICTURES)
1,2-Two of the three exterior GFCI type 120 volt receptacle weather covers are broken off and need to be replaced.
10.5 ELECTRICAL SYSTEM
Picture 1
Picture 2
Picture 3
Picture 4
Comments: MINOR REPAIRS, (REFER TO REPORT PICTURES)
1,2,3-The 240 volt sub-panel located beside the two 120 volt panels was blocked by a large cabinet and an in-use soft ice cream machine, so the interior of this panel was not inspected. Portions of the front cover are loose and are being held on with duct tape. The left side of the cover can be easily moved in and out and needs to be properly secured to the panel. One panel filler plate is missing, leaving the interior of the panel exposed. This is a potential high voltage safety issue that needs immediate attention. Recommend licensed electrical contractor install a filler plate and secure cover to panel.(safety issue)
10.6 EXTERIOR LIGHTS, SWITCHES, OUTLETS (Visible condition and operation)
Comments: INSPECTED
10.7 SERVICE ENTRANCE CABLE (Visible condition of cable, splices, house connection, porcelain insulators, mast, masthead or gooseneck, conduit and if limbs or vines are in the way. Service is run aerially overhead or buried underground. The home owner's responsibility starts after cable splice where aerial feed is connected to the house, and for a buried feed at the meter.)
Comments: INSPECTED
10.8 METER BASE TO PANEL (Visible condition of base, how its attached to house, all cables and connectors, look for illegal wire taps running to another panel or device which could severely overload the service utility drop and meter base, and does meter base amp rating closely match the fuse or circuit breaker panel amp rating.)
Comments: INSPECTED
10.9 PANELS, FUSE BOXES, AND SUB-PANELS (Visible condition. Checking panels for proper circuit or fuse labeling, all circuit breakers same brand name as panel, one main breaker or disconnect that cuts all power to house. Check that all wires to single-pole breakers are colored black and not white.)
Comments: INSPECTED
10.10 ELECTRICAL SYSTEM GROUND (Visible condition. A ground wire bleeds stray voltages to ground and current should not flow continuously in this wire. A ground wire from the neutral/grounding bus bar in main panel runs to a grounding electrode or rod. There should also be a ground wire from the main panel neutral/grounding bus bar to metal water pipes. Water pipes should be voltage free. Check water pipes for presence of voltage.)
Comments: INSPECTED
10.11 PANEL BONDING STRAP (Visible condition. A bonding strap or panel bond, is required in every main panel to connect the neutral/grounding bus bar to the panel frame so that the metal panel can't shock you if a live wire touches it.)
Comments: INSPECTED
10.12 ARE PANEL FILLER PLATES IN PLACE WITH NONE MISSING (Filler plates are little knockouts that are removed from panel front if breakers are installed. If no breaker was installed, this open spot is where someone could reach in and touch a hot spot.)
Comments: INSPECTED
10.13 ARE LOCATIONS OF PANELS AND SUB-PANELS READILY ACCESSIBLE (A countertop or workbench directly in front of panel makes it not readily accessible. A shorter person won't be able to reach and shut-off a breaker in an emergency.)
Comments: INSPECTED
10.14 IS THERE ONLY ONE WIRE TO EACH SERVICE ENTRY CABLE LUG IN MAIN PANEL (This is where the cable from meter connects into panel. Other wires, called illegal taps, on these two lugs are left without overcurrent protection. Don't confuse an illegal tap with surge-protection wiring where two small wires feed into main lugs and go to a small lightning-surge arrestor.)
Comments: INSPECTED
10.15 IS THERE ONLY ONE WIRE TO EACH BREAKER SCREW, NEUTRAL OR GROUND BUS SCREW, OR FUSE (Multiple wires are a sign of an overloaded panel and are dangerous because the wires can work loose from vibration and become a fire hazard. There is an exception to the rule: Square D, type-QO, size 15, 20, 30 amp breakers are listed for up to two 10 gauge wires.)
Comments: INSPECTED
10.16 ARE ALL WIRES TO EACH FUSE OR CIRCUIT BREAKER SIZED PROPERLY (This occurs if undersize wire is used with oversize breakers or fuses. This is critical so that whatever load is connected to the circuit breaker will be properly protected.)
Comments: INSPECTED
10.17 ARE ALL WIRES ON 15 0R 20 AMP CIRCUITS COPPER AND NOT SINGLE STRAND ALUMINUM (Aluminum wired homes built from 1965 to 1972 have had numerous problems with electrical connections to receptacles and switches.)
Comments: INSPECTED
10.18 IS PANEL FREE OF ANY WATER DAMAGE (The signs of moisture damage are brown iron stains and white corrosion on breakers and hot tabs inside panel.)
Comments: INSPECTED
10.19 IS PANEL FREE OF ANY DETERIORATION (Visible condition looking for signs of arcing, burn marks, blistering, or discoloration. If breaker wire connection has overheated, usually because it became loose, there will be discolored or burned insulation.)
Comments: INSPECTED
10.20 ARE SUB-PANEL GROUNDS ISOLATED FROM NEUTRALS (A sub-panels most common use is to provide a secondary panel some distance from the main service panel. In any sub-panel, grounds and neutrals must be kept separate from each other.)
Comments: INSPECTED
10.21 ARE APPROPRIATE OUTLETS GFCI PROTECTED (A Ground Fault Circuit Interrupter is a safety device that senses any shock hazard and interrupts the flow of electricity in the circuit. Receptacles requiring GFCIs are bathrooms, kitchen countertops, wet bar sinks, garages, pools, spa lights, and any outdoors below 6'6".)
Comments: INSPECTED
10.22 WERE A REPRESENTATIVE NUMBER OF OUTLETS TESTED (Verify proper outlet operation with a Suretest tester that tests for proper wiring, reversed polarity, voltage drop, ground impedance, Ground-to-Neutral voltage, line voltage, high resistance grounds, and false or bootleg grounds. The tester also verifies GFCI, ground fault circuit interrupter type outlets.
Comments: INSPECTED

HEATING SYSTEM

Styles & Materials
HEAT FOR:
LEFT SIDE ROOMS
LOCATION:
ROOF
FUEL SOURCE:
NATURAL GAS
HEAT TYPE:
FORCED AIR
ALL-IN-ONE PACKAGE UNIT
BTU RANGE:
120000 BTU INPUT/HR
96000 BTU OUTPUT/HR
HEAT SYSTEM BRAND:
CARRIER
MEASURED SUPPLY TEMP:
NOT MEASURED
NUMBER OF BURNER PORTS:
UNKNOWN
IGNITION SYSTEM:
ELECTRONIC AUTO PILOT
DUCTWORK:
INSULATED ROUND
INSULATED RECTANGULAR
MANUFACTURED:
12/2003
HEAT FOR:
RIGHT SIDE ROOMS
LOCATION:
ROOF
FUEL SOURCE:
NATURAL GAS
HEAT TYPE:
FORCED AIR
ALL-IN-ONE PACKAGE UNIT
BTU RANGE:
200000 BTU INPUT/HR
160000 BTU OUTPUT/HR
HEAT SYSTEM BRAND:
CARRIER
MEASURED SUPPLY TEMP:
NOT MEASURED
NUMBER OF BURNER PORTS:
UNKNOWN
DUCTWORK:
INSULATED ROUND
INSULATED RECTANGULAR
MANUFACTURED:
12/2003
IGNITION SYSTEM:
ELECTRONIC AUTO PILOT



Inspection Items
11.0 HEATING SYSTEM
Comments: MISCELLANEOUS INFORMATION
1-The two natural gas heating units located on the roof were not inspected. Since one units air conditioner was not functioning, there was a licensed heating and air contractor working on the units and the temperature was in the 90's where all interior workers were already hot. Annual system service is always recommended by a licensed heating an air contractor.
11.1 INSTALLED HEATING EQUIPMENT (Visible condition and check presence of conditioned air source in all rooms, furnace blower free of any excess noise or vibration, and return air filter is present and clean.)
Comments: INSPECTED
11.2 FLUE PIPE AND VENTING (Visible condition checking pipe rise, diameter, junction fit, screws, and clearances. A properly vented gas system exhausts combustion products to exterior and provides adequate oxygen for combustion.)
Comments: INSPECTED
11.3 COMBUSTION AIR SUPPLY (Combustion is a chemical reaction that occurs when fuel gases combine with oxygen and ignite. Visual inspection of flame characteristics is a good indicator of air/gas mixture problems that cause incomplete combustion.)
Comments: INSPECTED
11.4 WAS HEAT EXCHANGER TEST PROCEDURE DONE (This procedure ONLY applies to forced-air gas furnaces that use a blower to distribute heat. Procedure: Check the flame with blower off, then with blower on. If the main burner characteristics were normal with the blower off, but change or the flame lifts from the burner ports, the heat exchanger MAY be faulty.)
Comments: INSPECTED
11.5 WAS GAS FURNACE AREA CHECKED WITH SNIFFER AND FOUND FREE OF LEAKS
Comments: INSPECTED
11.6 WAS A TEMPERATURE MEASURED AT SUPPLY AND RETURN (Typical furnace operating temperatures are: NATURAL GAS: 130-140 degrees, OIL/PROPANE: 125-135 degrees, ELECTRIC: 110-120 degrees, HEAT PUMP: 95-100 degrees.)
Comments: INSPECTED
11.7 DISTRIBUTION SYSTEMS (Visible condition, checking fans, pumps, ducts and piping, insulation, air filters, registers, radiators, fan coil units and convectors)
Comments: INSPECTED
11.8 THERMOSTAT (Visible condition, checking if, level on wall, loose, equipment turns on/off from thermostat controls.)
Comments: INSPECTED

COOLING SYSTEM

Styles & Materials
COOLING FOR:
LEFT SIDE
MEASURED TEMP AT SUPPLY:
72 DEG
MEASURED TEMP AT RETURN:
86 DEG
CENTRAL AIR OUTSIDE UNIT:
CARRIER
CENTRAL AIR OUTSIDE UNIT:
MADE IN 12/2003
NUMBER OF TONS:
8 1/2
COOLING FOR:
RIGHT SIDE ROOMS
MEASURED TEMP AT SUPPLY:
73 DEG
MEASURED TEMP AT RETURN:
78 DEG
CENTRAL AIR OUTSIDE UNIT:
CARRIER
CENTRAL AIR OUTSIDE UNIT:
MADE IN 12/2003
NUMBER OF TONS:
12 1/2



Inspection Items
12.0 COOLING SYSTEM
Picture 1
Picture 2
Picture 3
Comments: FOR YOUR INFORMATION
1,2,3-There are two refrigeration condenser units located on the rear end of the roof and it appears one unit has been removed altogether where a service disconnect box still remains.
12.1 COOLING SYSTEM
Comments: MINOR REPAIRS, (REFER TO REPORT PICTURES)
1-The cooling unit located on the roof for the left side of the building has a 14 degree temperature differential from the return and supply vents. This is within the normal range of 14 to 22 degrees. The cooling unit for the right side of the building only had a 5 degree temperature differential then stopped working altogether. A licensed heating and air contractor was working on the units at the time of the inspection.

Left side unit: 48TFE is a 1-piece gas heating, electric cooling unit Single-Package STANDARD EFFICIENCY Roof Unit. It has a fully insulated cabinet, belt-drive evaporator fan motor, 2-inch disposable return air filter, and solid state heating controls with diagnostics. It uses R22 freon. (12.5 ton unit)

Right side unit: 48TME is a 1-piece gas heating, electric cooling unit Single-Package HIGH EFFICIENCY Roof Unit. It has a fully insulated cabinet, belt-drive evaporator fan motor, 2-inch disposable return air filter, and solid state heating controls with diagnostics. It uses R22 freon. (8.5 ton unit)
12.2 INSTALLED COOLING EQUIPMENT (Visible condition, checking condenser and evaporator units are free of any excess noise and vibration, condenser unit free of overgrowth, coil blockage, and sitting level on a slab.)
Comments: INSPECTED
12.3 OUTSIDE CONDENSER UNIT (Visible condition. It consists of compressor, coils, and blower fan. The compressor compresses low-pressure cold Freon gas, turning it into high pressure Freon gas that runs through the coils with the fan blowing across them to dissipate its heat, and condense into a hot Freon liquid. Warm air should be blowing when you walk by it outside.)
Comments: INSPECTED
12.4 INSIDE EVAPORATOR UNIT (Visible condition. It consists of a Freon metering device that is either an expansion valve or capillary tube, coils, and blower fan. Hot Freon liquid runs through the metering device, evaporates into cold, low-pressure Freon gas, runs through the coils that allow the gas to absorb heat and cool the house as the fan blows air through the coil and out ducts)
Comments: INSPECTED
12.5 CONDENSATION PAN AND LINES (Visible condition, checking for leaks, rust or deterioration and where the line terminates. The pan is where water extracted from the air by the evaporator runs into. Some systems use a pump to extract water out of the pan. Central air conditioning systems provide comfort cooling by lowering air temperature and removing excess moisture.)
Comments: INSPECTED
12.6 WAS TEMPERATURE DROP MEASUREMENT TAKEN FROM SUPPLY AND RETURN VENTS (A low drop could indicate low Freon charge. A high drop could indicate a dirty coil, filter or blower. There are other reasons why the temperature drop is out of range such as thermostat calibration and humidity.)
Comments: INSPECTED
12.7 IS COOLING UNIT ADEQUATE FOR SIZE OF HOUSE (The general rule of thumb is 1 ton for every 550 square feet of living space.)
Comments: INSPECTED

CRAWLSPACE, FOUNDATION INTERIOR

Styles & Materials
FOUNDATION INFORMATION:
FULL CONCRETE SLAB



Inspection Items
13.0 BASEMENT, CRAWLSPACE, FOUNDATION INTERIOR
Comments: FOR YOUR INFORMATION
The concrete slab foundation interior inspection was limited because most areas were finished with floor coverings. The concrete slab contains embedded water drainage pipes. All heating an air ducts are located within the attic. The water drains located in the left side refrigeration room were adequately draining at the time of the inspection. This is good!

COMPLIMENTARY PHOTOS


 



Inspection Items
14.0 COMPLIMENTARY PHOTOS
Picture 1
Picture 2
Picture 3
Picture 4
Picture 5
Picture 6
Picture 7
Picture 8
Picture 9
Picture 10
Picture 11
Picture 12
Comments: FOR YOUR INFORMATION
1,2,3,4,5,6,7,8,9,10,11,12-Complimentary photos.

Prepared Using HomeGauge http://www.homegauge.com/ SHGI (c) 2000-2003 : Licensed To Jeffrey James Aiken