www.acehomeinspections.net

P.O. Box 1993
Alabaster, Alabama 35007
(205)401-3030

Customer
Sample

Home
Sample

Real Estate Agent
Sample

Inspection Date 
Friday, June 08, 2007
Weather:
Clear and Sunny
Report ID:
06360 FINAL REPORT
Temperature:
85 to 90 degrees
Inspected By 
Jeff Aiken

SUMMARY


www.acehomeinspections.net

P.O. Box 1993
Alabaster, Alabama 35007
(205)401-3030

Customer
Sample

Home
Sample

The following items or discoveries indicate that these systems or components do not function as intended or adversely affects the habitabilty of the dwelling; or appear to warrant further investigation by a specialist, or requires subsequent observation.

This summary shall not contain recommendations for routine upkeep of a system or component to keep it in proper functioning condition or recommendations to upgrade or enhance the function, efficiency, or safety of the home.

This Summary is not the entire report. The complete report may include additional information of concern to the customer. It is recommended that the customer read the complete report.

REPORT ORGANIZATION INFORMATION
1.0 REPORT ORGANIZATION INFORMATION
FOR YOUR INFORMATION
A GENERAL SUMMARY OF ITEMS THAT NEED ADDRESSING IS AT THE BEGINNING BEFORE THE REPORT INVOICE. THE SUMMARY CONTAINS NO PHOTOGRAPHS. ALL PHOTOGRAPHS ARE IN THE MAIN REPORT. FOR EXAMPLE SUMMARY SECTION 3.1 IS THE SAME AS MAIN REPORT SECTION 3.1 MINUS THE PHOTOGRAPHS.

SECTIONS 2 THROUGH 20 HAVE ALL THE PHOTOGRAPHS AND LIST ALL ITEMS UNCOVERED DURING THE INSPECTION.

SECTIONS 22 THROUGH 34 CONTAIN NO PHOTOGRAPHS AND ARE A LISTING OF ALL ITEMS INSPECTED AND CONTAINS ALL BUILDING STYLES AND GENERAL INFORMATION ALONG WITH MEASURED ITEMS SUCH AS HEATING UNIT TEMPERATURES AND WATER HEATER MANUFACTURE DATES.

FOR YOUR INFORMATION IT APPEARS BASED ON WATER HEATER AND HEATING AND COOLING UNIT DATES, THAT MAJOR BUILDING RENOVATIONS TOOK PLACE IN LATE 1993 AND 1994. THE BUILDING HAS A TOTAL OF 14 SEPARATE UNITS. UNIT 5 IS THE ONLY ONE BEDROOM UNIT. ALL OTHERS HAVE TWO BEDROOMS. OVERALL BUILDING STRUCTURE APPEARED ADEQUATE AND ROBUST WITH NUMEROUS MINOR AND SAFETY REPAIRS NEEDED.

BUILDING EXTERIOR
2.5 BUILDING EXTERIOR
MISCELLANEOUS INFORMATION, (REFER TO REPORT PICTURES)
1,2,3-ACE Home Inspections, LLC does not inspect E.I.F.S. (Exterior Insulation and Finish System) style siding. ACE Home Inspections, LLC is not a state licensed E.I.F.S. inspection company and always advises its clients to contact a state licensed E.I.F.S. contractor to obtain the proper condition of the buildings E.I.F.S. that includes a moisture content analysis and that follows all state E.I.F.S. inspection rules and regulations. The E.I.F.S. type of siding is located on the front wall of the building. E.I.F.S. is similar to a Dry-vit or Stucco type siding.
2.6 BUILDING EXTERIOR
MISCELLANEOUS INFORMATION, (REFER TO REPORT PICTURES)
1,2-The top railing or parapet metal flashing or coping has started to oxidize. There is also one section that is raised up because it has two small attached satellite TV dishes. Repairs are recommended which may include but are not limited to painting of oxidized areas and proper attachment of the one raised area.

2,3,4,5,6,7,8,9,10,11,12-These are photos of the bitumen roof covering material. There are about a half dozen large low spots where standing water does not properly drain away, and collects until it evaporates. The roof is supposed to properly angled where all water drains down the center PVC drains that travel through the attic and out both sides of the rear wall and down to the street. Standing water is never recommended because this can break down the roof covering slowly over time. The present bitumen roof covering appears overall aged with numerous spider web type cracking, low areas, and numerous bunched up, raised, or rippled areas and some of the roof tar coatings around the roof penetrations is aged with cracks and gaps. There were no areas of interior wood roof decking that was moisture ridden or wet at the time of inspection. There was moisture discoloration, but all areas appeared to be structurally adequate at the time of the inspection.

Recommend further investigation of overall roof adequacy and repairs by a licensed roof contractor which may include but are not limited to resurface the low areas where water collects and reseal around all roof penetrations and possibly resurfacing entire roof with a protective coating such as an asphalt-based emulsion. This should improve and prolong overall roof covering adequacy and life expectancy. Maintaining roof involves resurfacing with a protective coating such as an asphalt-based emulsion every 3 to 6 years.

13,14,15,16,17-Some of the upper rear and front bottom or sill exterior wood window framing is moisture deteriorated and the paint finish on the front and left side lower window framing is aged with peeled and missing areas where repairs are recommended. Repairs may include but are not limited to repair/replacement of upper window sills where needed, and heavily painting of all exterior wood members.

18-The rear cable lid is open because it has some slight damage. This is beyond the scope of the inspection, however is listed as a courtesy.
2.7 BUILDING EXTERIOR
MISCELLANEOUS INFORMATION, (REFER TO REPORT PICTURES)
1,2,3,4,5,6,7,8-The majority of the mortar between the bricks is aged where it is somewhat soft with a sand-like composition and can be poked or pried away. The deterioration is spread out in various location. The brick siding still appears overall adequate with no major areas of cracking. There are a couple small hairline stairstep cracks one along the right side at the top of the front corner and the other along the right side at the top of the rear corner. There is no side-to-side differential where one side is not out further than other, indicating normal settlement or aging. There are also numerous bricks which have missing sections, primarily throughout the entire right side. The combination of the soft mortar and chaffing or missing and broke off sections of brick do not appear to significantly effect the overall structure because no major cracking has developed, however warrants further investigation by a licensed brick mason or brick siding contractor. This is because even though no major deterioration exists today, the sift mortar and brick deterioration could create issue in the near future? Deteriorated mortar joints are entry spots for water. Proper mortar joints have no gaps or missing mortar and are shaped in a way that diverts water out of the joint. When mortar deteriorates from exposure to weather it becomes much more absorbent. A common repair for mortar joints is called repointing or tuckpointing. In this process, the existing mortar joint is cut out and repacked with new mortar compound.

9-The brick siding along one corner of the concrete slab base for the rear stairwell is severely deteriorated where repairs by a licensed siding or brick mason contractor is recommended.

BUILDING INTERIOR
3.3 BUILDING INTERIOR
MINOR REPAIRS, (REFER TO REPORT PICTURES)
1-There is a moisture discolored and deteriorated section of plasterboard wall located to the right of the second floor exit door of Unit 4. The other side of the wall in Unit 4 was found to be adequate. Lifting the ceiling tiles above the door within Unit 4 revealed an area of moisture discolored roof decking boards. All areas were dry at the time of the inspection, indicating a previously repaired leak where the wall was never repaired/painted. Recommend owner disclosure of any previous repairs to roof covering above this area along with repairs to plasterboard. (cosmetic)

2-The upper and lower hallway carpets are dirty.

3,4,5,6-The second floor hallway center building exit stairwell emergency light fixture does not operate. The stairwell is pitch dark and a safety hazard. The main ceiling light bulb is broke off and the emergency light should be in operation. There also a couple ceiling tiles that severely moisture discolored. The tub in Unit 5 is located directly overtop the stairwell. The shower was operated for some time while this was investigated. No water leaks were uncovered, indicating this most likely has been repaired. Recommend installation of new ceiling tiles and repair of both light fixtures. (safety issue)

7-There are some small junction boxes located throughout the attic above the second floor hallway where the installation of proper covers is recommended.

8,9,10-The plywood roof decking around the rear most center roof drain closest to the roof entry scuttle hole has some discolorations indicating previous leakage. The area was dry at the time of inspection, however since all drains could not be accessed or were not readily accessible a licensed roof contractor is recommended for further investigation. Repairs may include but are not limited to sealing around all the center drains on top of the roof since the roof covering appears aged.

LAUNDRY ROOM
4.1 LAUNDRY ROOM
MISCELLANEOUS INFORMATION, (REFER TO REPORT PICTURES)
1,2,3-The laundry room outlets tested are properly grounded, however the outlet above the small table is within six feet of the wash tub sink and is NOT GFCI protected. Recommend this one outlet be upgraded with GFCI protection by a licensed electrical contractor. (safety)

MAINTENANCE ROOM
6.4 MAINTENANCE ROOM
MINOR REPAIRS, (REFER TO REPORT PICTURES)
1-The maintenance room door does not solidly closed or lock. This room has a panel where keys can be accessed to each unit where repairs and robust locking of this room is recommended.

OTHER ITEMS:
-The management has a key to unlock all units except Unit 1. This unit was able to be accessed after the tenants came home for the evening. Recommend a key to Unit 1 be made and placed with rest of unit keys.

UNIT 1
7.1 UNIT 1
MINOR REPAIRS, (REFER TO REPORT PICTURES)
1-The light switch beside the front entry door is missing a cover (safety)

2-Another layer of floor tiles has been installed in the half bathroom. Some of these tiles are missing or are loose.

3-There is a small opening beside the kitchen faucet where a vegetable spray wand or snap-in plug/cover is recommended.

4-The upper bathroom floor tiles are deteriorated along the entry door.

5-The light switch in the upper rear bedroom is missing a cover. (safety)

OTHER ITEMS:
-The oven handle is loose.
-The metal suspended ceiling squares are rusty where painting is recommended.
-The upper bathroom sink drains slow where repairs are recommended which may include but are not limited to the use of a liquid drain cleaner or removal of drain piping for cleaning.
-The half bathroom commode tank water stays running.
-The upper bathroom commode does not flush sometimes because the tank does not always fill with water after flushed.
-The air conditioner measure temperature drop between the supply and return vents was only 8 degrees and NOT within the normal 14 to 25 degree range. System service and repairs by a licensed heat and air contractor is recommended.

UNIT 2
8.1 UNIT 2
MINOR REPAIRS, (REFER TO REPORT PICTURES)
1-The carpet is loose at the upper bathroom threshold entry.

OTHER ITEMS:
-One set of upper bedroom bi-fold closet doors is missing.
-The lower section of the second floor stairway wood banister is loose.
-The kitchen sink aerator is aged and sprays water upward when water is turned on too much.
-The dishwasher makes loud noises occasionally. The motor may be going bad where further investigation and repair by a licensed contractor is recommended.

UNIT 3
9.2 UNIT 3
MINOR REPAIRS, (REFER TO REPORT PICTURES)
1-One upper kitchen cabinet door has been removed.

2-The 4 top elements were not turned on because of owner items.

3-The cabinet door under the kitchen sink is off the hinges.

4-The floor tiles in the kitchen are in place, however some have some gaps between them. (cosmetic)

5-Recommend caulking where tub meets the floor.

OTHER ITEMS:
-The garbage disposal does not operate.
-The half bathroom pedestal sink is loose where it mounts to the wall.
-The living room coat closet door is difficult to operate.
-The lower section of the second floor stairway wood banister is loose.

UNIT 4
10.1 UNIT 4
MINOR REPAIRS, (REFER TO REPORT PICTURES)
1-An 18 inch section of formica has come loose behind the kitchen sink faucet.

2-The front right stove element does not turn on.

3-The half bathroom exhaust fan vent hose to the exterior is missing.

4-The tub faucet has a constant water drip.

5-The caulking behind the upper bathroom wall sink is aged.

6-Wiring and wire-nuts are hanging loose below the light fixture over the kitchen sink.

7-The half bathroom GFCI type outlet no longer trips or resets where repairs are recommended.

OTHER ITEMS:
-The garbage disposal does not operate.
-Some walls and doors need to be painted.

UNIT 5
11.1 UNIT 5
MINOR REPAIRS, (REFER TO REPORT PICTURES)
1-The floor coverings are very dirty. (cosmetic)

OTHER ITEMS:
-The vinyl flooring in the bathroom is curled up along the base of the tub.
-The oven element would not turn on.
-The bathroom exhaust fan does not operate.

UNIT 6
12.1 UNIT 6
MINOR REPAIRS, (REFER TO REPORT PICTURES)
1-The carpets are dirty.

OTHER ITEMS:
-The oven handle is loose.
-The half bathroom sink stopper needs repairs.
-The half bathroom towel rod is loose.
-The kitchen flooring has some stains.
-The tub faucet has a constant water drip.
-The lower section of the second floor stairway wood banister is loose.
-The sink stopper in the upper bathroom needs repairs.
-The garbage disposal does not operate.

UNIT 7
13.1 UNIT 7
MINOR REPAIRS, (REFER TO REPORT PICTURES)
1-An area of dining wall has been patched with wallboard compound, however needs sanded and painted. (cosmetic)

2-A small hole in the living room wall needs patched.

3-An area of floor tiles under the upper bathroom wall sink are deteriorated.

4-The carpet is loose at the upper bathroom entry.

5-An 18 inch section of formica has come loose behind the kitchen sink faucet.

6-The dining room ceiling mounted smoke alarm is missing.

OTHER ITEMS:
-The carpets are dirty.
-The upper bathroom sink stopper needs repairs.
-The air conditioner measure temperature drop between the supply and return vents was only 0 degrees and NOT within the normal 14 to 25 degree range. System service and repairs by a licensed heat and air contractor is recommended.

UNIT 8
14.1 UNIT 8
MINOR REPAIRS, (REFER TO REPORT PICTURES)
OTHER ITEMS:
-The dining room ceiling mounted smoke alarm is missing.
-The garbage disposal does not operate.
-There are 2 small chipped areas out of the countertop above the dishwasher,
-The toilet [paper holder is loose.
-The upper bathroom sink stopper needs repairs.
-The tub has a constant water drip.
-The front entry door knob is aged where replacement is recommended.
-The thermostat is severely loose and hanging crooked where it mounts to the wall.
-The air conditioner measure temperature drop between the supply and return vents was only 10 degrees and NOT within the normal 14 to 25 degree range. System service and repairs by a licensed heat and air contractor is recommended.

UNIT 9
15.1 UNIT 9
MINOR REPAIRS, (REFER TO REPORT PICTURES)
OTHER ITEMS:
-The oven handle is loose.
-There is a small patched area of wall beside the living room closet door where sanding and painting is recommended. (cosmetic)
-The half bathroom pedestal sink is loose where it mounts to the wall.
-The heat pump electric coil emergency heat measured only 78 degrees where further investigation by a licensed heat and air contractor is recommended,
-One side of the bi-fold closet doors in the rear bedroom have been removed and placed in the hallway.

UNIT 10
16.1 UNIT 10
MINOR REPAIRS, (REFER TO REPORT PICTURES)
1-The bottom refrigerator door seal has come loose and sticks to the bottom of the refrigerator casing. This sticking is noticed when the door is opened or closed. The area of metal behind the seal has become very corroded. Tenant states hastily repairs were previously made by trying to glue seal on and paint bottom of door where seal now sticks to paint.

OTHER ITEMS:
-The oven handle is loose.
-The deadbolt for the second floor entry door does not fully engage because the hole in the door frame is not deep enough.
-The upper bathroom sink stopper needs repairs.

UNIT 11
17.1 UNIT 11
MINOR REPAIRS, (REFER TO REPORT PICTURES)
1-The top part of the left cabinet door under the sink is missing leaving a noticeable gap.

2-The half bathroom pedestal sink has a sizeable water leak on the drain piping where water was observed on the floor.

3-There are a couple small gouges on the living room wall.

4-A 16 inch circular area of carpet at the front entry door at the bottom of stairs is ripped and snagged.

OTHER ITEMS:
-The light over the kitchen sink does not turn on.
-The tub has a constant water drip.

UNIT 12
18.1 UNIT 12
MINOR REPAIRS, (REFER TO REPORT PICTURES)
1-The right rear stove element does not turn on.

2-A section of plasterboard wall in the closet under the stairs has been cut for some reason.

3-The electrical panel cover could not be opened or removed because a large expensive and heavy wall picture light and a large 40 gallon lower fish tank are blocking it.

4-The GFCI type outlet in the upper bathroom has no power because it will no longer reset where replacement is recommended by a licensed electrical contractor.

OTHER ITEMS:
-The garbage disposal does not operate.
-The floor tiles in the kitchen are aged, but functional. (cosmetic)
-The carpets are dirty.
-The interior side of the front entry door needs painted.
-The tub has a constant water drip.

UNIT 13
19.3 UNIT 13
MINOR REPAIRS, (REFER TO REPORT PICTURES)
OTHER ITEMS:
-The thermostat is loose where it mounts to the wall.
-The carpet is dirty.
-The pedestal sink is loose where it mounts to the wall.
-The lower dining room double pane fixed window has some minor fogging along the bottom edges and the surrounding wall enclosure needs painted.
-One side of the upper bathroom toilet tissue holder is missing.
-The upper bathroom towel rod is loose.
-The upper bathroom wall sink is loose.
-The tub has a constant water drip.

UNIT 14
20.2 UNIT 14
MINOR REPAIRS, (REFER TO REPORT PICTURES)
1-Water heater has had covers removed. Replacement is recommended both for safety and efficiency reasons. (safety issue)

2-The upper bedroom double pane fixed windows have some minor fogging along the bottom edges and the surrounding wall enclosure needs painted.

3-The tub floor is stained where heavy cleaning will be required.

OTHER ITEMS:
-The thermostat is loose where it mounts to the wall.
-The dishwasher is loose and needs to be secured to the countertop.
-The oven handle is loose.
-The carpet along the upper bathroom entry is loose and frayed.

www.acehomeinspections.net

Home inspectors are not required to report on the following: Life expectancy of any component or system; The causes of the need for a repair; The methods, materials, and costs of corrections; The suitability of the property for any specialized use; Compliance or non-compliance with codes, ordinances, statutes, regulatory requirements or restrictions; The market value of the property or its marketability; The advisability or inadvisability of purchase of the property; Any component or system that was not observed; The presence or absence of pests such as wood damaging organisms, rodents, or insects; or Cosmetic items, underground items, or items not permanently installed. Home inspectors are not required to: Offer warranties or guarantees of any kind; Calculate the strength, adequacy, or efficiency of any system or component; Enter any area or perform any procedure that may damage the property or its components or be dangerous to the home inspector or other persons; Operate any system or component that is shut down or otherwise inoperable; Operate any system or component that does not respond to normal operating controls; Disturb insulation, move personal items, panels, furniture, equipment, plant life, soil, snow, ice, or debris that obstructs access or visibility; Determine the presence or absence of any suspected adverse environmental condition or hazardous substance, including but not limited to mold, toxins, carcinogens, noise, contaminants in the building or in soil, water, and air; Determine the effectiveness of any system installed to control or remove suspected hazardous substances; Predict future condition, including but not limited to failure of components; Since this report is provided for the specific benefit of the customer(s), secondary readers of this information should hire a licensed inspector to perform an inspection to meet their specific needs and to obtain current information concerning this property.

www.acehomeinspections.net

Prepared Using HomeGauge http://www.homegauge.com/ SHGI (c) 2000-2003 : Licensed To Jeffrey James Aiken

 

REPORT ORGANIZATION INFORMATION


 



Inspection Items
1.0 REPORT ORGANIZATION INFORMATION
Comments: FOR YOUR INFORMATION
A GENERAL SUMMARY OF ITEMS THAT NEED ADDRESSING IS AT THE BEGINNING BEFORE THE REPORT INVOICE. THE SUMMARY CONTAINS NO PHOTOGRAPHS. ALL PHOTOGRAPHS ARE IN THE MAIN REPORT. FOR EXAMPLE SUMMARY SECTION 3.1 IS THE SAME AS MAIN REPORT SECTION 3.1 MINUS THE PHOTOGRAPHS.

SECTIONS 2 THROUGH 20 HAVE ALL THE PHOTOGRAPHS AND LIST ALL ITEMS UNCOVERED DURING THE INSPECTION.

SECTIONS 22 THROUGH 34 CONTAIN NO PHOTOGRAPHS AND ARE A LISTING OF ALL ITEMS INSPECTED AND CONTAINS ALL BUILDING STYLES AND GENERAL INFORMATION ALONG WITH MEASURED ITEMS SUCH AS HEATING UNIT TEMPERATURES AND WATER HEATER MANUFACTURE DATES.

FOR YOUR INFORMATION IT APPEARS BASED ON WATER HEATER AND HEATING AND COOLING UNIT DATES, THAT MAJOR BUILDING RENOVATIONS TOOK PLACE IN LATE 1993 AND 1994. THE BUILDING HAS A TOTAL OF 14 SEPARATE UNITS. UNIT 5 IS THE ONLY ONE BEDROOM UNIT. ALL OTHERS HAVE TWO BEDROOMS. OVERALL BUILDING STRUCTURE APPEARED ADEQUATE AND ROBUST WITH NUMEROUS MINOR AND SAFETY REPAIRS NEEDED.

BUILDING EXTERIOR


 



Inspection Items
2.0 BUILDING EXTERIOR
Comments: FOR YOUR INFORMATION
House siding is brick, entry doors and framing are metal, and the windows are aluminum which are relatively low maintenance, however the window framing is wood and subject to deterioration if not properly maintained. It is strongly recommended that all exterior wood be painted on a periodic basis. The whole point is to prevent moisture damage which leads to costly total replacement. IT CAN NOT BE STRESSED ENOUGH THAT PERIODIC PAINTING OF ALL WOOD SURFACES IS A MUST!!! Whenever small cracks start to develop at the end of the boards, it is time to paint! (Maintenance tip.)
2.1 BUILDING EXTERIOR
Picture 1
Picture 2
Picture 3
Picture 4
Picture 5
Picture 6
Comments: FOR YOUR INFORMATION
1-Front view from roof.
2-Rear view from roof.
3-Left side view from roof.
4-Right side view from roof.
5-Sode view from rear street.
6--Electrical service comes from underground conduit and appeared adequate and was properly grounded to a ground rod, as shown. This is good! Each Unit has their own electric meter.
2.2 BUILDING EXTERIOR
Picture 1
Picture 2
Comments: FOR YOUR INFORMATION
1,2-There is 6 to 8 inch clearance between the separate building on the right side which appears to be adequate for venting purposes.
2.3 BUILDING EXTERIOR
Comments: FOR YOUR INFORMATION
The flat bitumen built-up style roof has a parapet. It is a low wall along the perimeter where it modifies the wind flow over the roof so that the pressure on it is more uniformly distributed. It also provides a measure of safety in that no objects are so easily blown into the street below. Built-up roof systems are composed of three materials. They are bitumen, felts, and surfacing. Together they create a strong watertight membrane. A gravel stop around the perimeter along the parapet provides a finished edge for the built-up roofing, Not all built-up roofs have a top surface covered with aggregates. To maintain the weathering surface in reasonably good condition, the surface should be covered with a protective coating such as an asphalt based emulsion every three to six years.

Roof penetrations include 6 center drain vents, 8 air conditioner line portals, 4 air exhaust flues, 10 plumbing vents, and an entry scuttle hole. All bathroom exhaust fans vent through central exhaust lines that terminate through the far rear end of the roof near the entry scuttle hole. Water drains off the flat roof through the drains located in the middle and all air conditioner lines enter through the portal pipes.
2.4 BUILDING EXTERIOR
Picture 1
Picture 2
Picture 3
Picture 4
Comments: MISCELLANEOUS INFORMATION
1-Public concrete walkways have some shrinkage or hairline cracks. (These type cracks are normal, cosmetic, usually not serious and may have been caused from original concrete mix problems or from settlement after building was constructed. Most likely there should not be a problem, if the cracks have not worsened with time.) The curbs have some areas of deterioration or crumbling.

2,3-The rear second floor entrance metal stairwell appeared structurally adequate and robust and proper hand-rails were observed. The center interior stairwell exit door is metal and appeared structurally adequate and had a proper hand-rail. This is good, however some areas of corrosion were observed on the exterior stairwell where heavily painting of all areas is recommended. (Maintenance tip.)

4-Main building water meter is located in the rear.


2.5 BUILDING EXTERIOR
Picture 1
Picture 2
Picture 3
Comments: MISCELLANEOUS INFORMATION, (REFER TO REPORT PICTURES)
1,2,3-ACE Home Inspections, LLC does not inspect E.I.F.S. (Exterior Insulation and Finish System) style siding. ACE Home Inspections, LLC is not a state licensed E.I.F.S. inspection company and always advises its clients to contact a state licensed E.I.F.S. contractor to obtain the proper condition of the buildings E.I.F.S. that includes a moisture content analysis and that follows all state E.I.F.S. inspection rules and regulations. The E.I.F.S. type of siding is located on the front wall of the building. E.I.F.S. is similar to a Dry-vit or Stucco type siding.
2.6 BUILDING EXTERIOR
Picture 1
Picture 2
Picture 3
Picture 4
Picture 5
Picture 6
Picture 7
Picture 8
Picture 9
Picture 10
Picture 11
Picture 12
Picture 13
Picture 14
Picture 15
Picture 16
Picture 17
Picture 18
Comments: MISCELLANEOUS INFORMATION, (REFER TO REPORT PICTURES)
1,2-The top railing or parapet metal flashing or coping has started to oxidize. There is also one section that is raised up because it has two small attached satellite TV dishes. Repairs are recommended which may include but are not limited to painting of oxidized areas and proper attachment of the one raised area.

2,3,4,5,6,7,8,9,10,11,12-These are photos of the bitumen roof covering material. There are about a half dozen large low spots where standing water does not properly drain away, and collects until it evaporates. The roof is supposed to properly angled where all water drains down the center PVC drains that travel through the attic and out both sides of the rear wall and down to the street. Standing water is never recommended because this can break down the roof covering slowly over time. The present bitumen roof covering appears overall aged with numerous spider web type cracking, low areas, and numerous bunched up, raised, or rippled areas and some of the roof tar coatings around the roof penetrations is aged with cracks and gaps. There were no areas of interior wood roof decking that was moisture ridden or wet at the time of inspection. There was moisture discoloration, but all areas appeared to be structurally adequate at the time of the inspection.

Recommend further investigation of overall roof adequacy and repairs by a licensed roof contractor which may include but are not limited to resurface the low areas where water collects and reseal around all roof penetrations and possibly resurfacing entire roof with a protective coating such as an asphalt-based emulsion. This should improve and prolong overall roof covering adequacy and life expectancy. Maintaining roof involves resurfacing with a protective coating such as an asphalt-based emulsion every 3 to 6 years.

13,14,15,16,17-Some of the upper rear and front bottom or sill exterior wood window framing is moisture deteriorated and the paint finish on the front and left side lower window framing is aged with peeled and missing areas where repairs are recommended. Repairs may include but are not limited to repair/replacement of upper window sills where needed, and heavily painting of all exterior wood members.

18-The rear cable lid is open because it has some slight damage. This is beyond the scope of the inspection, however is listed as a courtesy.
2.7 BUILDING EXTERIOR
Picture 1
Picture 2
Picture 3
Picture 4
Picture 5
Picture 6
Picture 7
Picture 8
Picture 9
Comments: MISCELLANEOUS INFORMATION, (REFER TO REPORT PICTURES)
1,2,3,4,5,6,7,8-The majority of the mortar between the bricks is aged where it is somewhat soft with a sand-like composition and can be poked or pried away. The deterioration is spread out in various location. The brick siding still appears overall adequate with no major areas of cracking. There are a couple small hairline stairstep cracks one along the right side at the top of the front corner and the other along the right side at the top of the rear corner. There is no side-to-side differential where one side is not out further than other, indicating normal settlement or aging. There are also numerous bricks which have missing sections, primarily throughout the entire right side. The combination of the soft mortar and chaffing or missing and broke off sections of brick do not appear to significantly effect the overall structure because no major cracking has developed, however warrants further investigation by a licensed brick mason or brick siding contractor. This is because even though no major deterioration exists today, the sift mortar and brick deterioration could create issue in the near future? Deteriorated mortar joints are entry spots for water. Proper mortar joints have no gaps or missing mortar and are shaped in a way that diverts water out of the joint. When mortar deteriorates from exposure to weather it becomes much more absorbent. A common repair for mortar joints is called repointing or tuckpointing. In this process, the existing mortar joint is cut out and repacked with new mortar compound.

9-The brick siding along one corner of the concrete slab base for the rear stairwell is severely deteriorated where repairs by a licensed siding or brick mason contractor is recommended.

BUILDING INTERIOR


 



Inspection Items
3.0 BUILDING INTERIOR
Comments: FOR YOUR INFORMATION
Attic areas have insulation with an R-value or resistance to heat loss value of R-19.

3.1 BUILDING INTERIOR
Picture 1
Picture 2
Picture 3
Comments: FOR YOUR INFORMATION
1-The roof is accessed through a scuttle hole located at the rear end of the upper hallway, just outside Unit 13. The metal door is hinged and opens into the hallway attic area. The actual roof opening has a tin cover that is secured in place with two screws. The top cover was secured back in place after the roof inspection.

2-Upper hallway.

3-Lower hallway.
3.2 BUILDING INTERIOR
Picture 1
Picture 2
Picture 3
Picture 4
Picture 5
Picture 6
Picture 7
Picture 8
Picture 9
Picture 10
Picture 11
Picture 12
Picture 13
Picture 14
Picture 15
Comments: FOR YOUR INFORMATION
1,2,3,4-Hallways have appropriate fire extinguishers, exit signs, and smoke alarms and emergency light fixtures. This is good! Some interior walls have some slight moisture discolorations along the rear doors. All areas were dry to the touch at the time of inspection. Recommend painting hallway walls and ceilings. (cosmetic issue)

5,6,7,8,9,10,11-Both the first and second floor hallway attics are accessed through a series of ceiling scuttle holes. The scuttle holes are all structurally adequate and robust with metal framing and hinged metal doors. The following photos are a sampling of the hallway attic areas. The majority of the roof decking in the second floor attic and floor decking in the first floor attic appeared adequate and relatively free of moisture discoloration and deterioration. Building construction consists of robust 12 inch steel beams and wood rafters and ceiling joists. It appears that at one time in the past there was a fire, based on some of the rear second floor attic wood members which were charred and burnt. It appears that the majority of the deteriorated wood members have been removed. The remaining original wood members have been structurally strengthened with new wood members. Proper plasterboard firewalls were observed along the lengths of the attics. A random sampling of first and second floor hallway attics were inspected around scuttle holes. Attempts were made to travel the length of the hallway attics, however most areas were blocked with pipes and structural members, causing low clearance or inaccessible areas. This report pertains to the visible areas inspected and not inaccessible and low clearance areas.

12,13,14-Front entry can be obtained by using the intercom and having tenant unlatch door from control unit located in each individual apartment or from regular key access. ACE Home Inspections, LLC does not inspect intercoms, keyless type entry entry systems, security systems, or video surveillance systems.

15-Tenant mailboxes are located in the space between the entry doors.
3.3 BUILDING INTERIOR
Picture 1
Picture 2
Picture 3
Picture 4
Picture 5
Picture 6
Picture 7
Picture 8
Picture 9
Picture 10
Comments: MINOR REPAIRS, (REFER TO REPORT PICTURES)
1-There is a moisture discolored and deteriorated section of plasterboard wall located to the right of the second floor exit door of Unit 4. The other side of the wall in Unit 4 was found to be adequate. Lifting the ceiling tiles above the door within Unit 4 revealed an area of moisture discolored roof decking boards. All areas were dry at the time of the inspection, indicating a previously repaired leak where the wall was never repaired/painted. Recommend owner disclosure of any previous repairs to roof covering above this area along with repairs to plasterboard. (cosmetic)

2-The upper and lower hallway carpets are dirty.

3,4,5,6-The second floor hallway center building exit stairwell emergency light fixture does not operate. The stairwell is pitch dark and a safety hazard. The main ceiling light bulb is broke off and the emergency light should be in operation. There also a couple ceiling tiles that severely moisture discolored. The tub in Unit 5 is located directly overtop the stairwell. The shower was operated for some time while this was investigated. No water leaks were uncovered, indicating this most likely has been repaired. Recommend installation of new ceiling tiles and repair of both light fixtures. (safety issue)

7-There are some small junction boxes located throughout the attic above the second floor hallway where the installation of proper covers is recommended.

8,9,10-The plywood roof decking around the rear most center roof drain closest to the roof entry scuttle hole has some discolorations indicating previous leakage. The area was dry at the time of inspection, however since all drains could not be accessed or were not readily accessible a licensed roof contractor is recommended for further investigation. Repairs may include but are not limited to sealing around all the center drains on top of the roof since the roof covering appears aged.
3.4 BUILDING INTERIOR
Comments: FOR YOUR INFORMATION
ACE Home Inspections, LLC only tests a random sampling of house smoke alarms always recommends that ALL smoke alarms be tested and replaced if found defective before moving in.

Smoke alarms are always recommended in all hallways, bedrooms, and kitchens.
3.5 BUILDING INTERIOR
Comments: FOR YOUR INFORMATION
ACE Home Inspections, LLC is not a licensed air quality, odor, or environmental expert and makes no conclusions as to any of the homes various odors or air quality other than noting any obvious apparent markings on floor coverings from normal wear and tear or from animals such as dogs, cats, or rodents. ACE Home Inspections, LLC always recommends used carpets be properly cleaned by a licensed carpet contractor and an air quality or environmental expert be contacted if client recognizes or concludes themselves that any apparent odors are present, before closing. ACE Home Inspections, LLC does not dismantle or open any non readily accessible areas such as air vents or ductwork and does not move objects or furniture and is not responsible for hidden or latent defects of any kind such as any cracked tile or torn and soiled carpet under furniture. ACE Home Inspections, LLC offers no warranties or guarantees and lists all conditions at the time of inspection, where the inspection is like a snapshot in time. For example a component proved to be in working order at time of inspection, could be malfunctioning soon after moving in at no fault of ACE Home Inspections, LLC.
3.6 BUILDING INTERIOR
Comments: FOR YOUR INFORMATION
ACE Home Inspections, LLC offers no warranties or guarantees. A home inspection is like a snap shot in time where component conditions are noted at the time of inspection. ACE Home Inspections, LLC is not responsible for component conditions occurring after the time of the inspection.

LAUNDRY ROOM


 



Inspection Items
4.0 LAUNDRY ROOM
Picture 1
Picture 2
Picture 3
Picture 4
Picture 5
Picture 6
Comments: FOR YOUR INFORMATION
1,2------UPGRADE-----Washer hoses that are original black hose type and susceptible to sudden leaking. It is recommended, but not required, that new wire braided permanent type hoses always be installed. See picture for an example of wire braided hoses that can be purchased at hardware and appliance stores.

3,4,5,6-There is an attic section above the laundry room that is accessed through a metal door and framed ceiling scuttle hole. The attic contains the heating an air unit for the small upstairs one bedroom unit 5. There are vents going to the laundry room ceiling that are closed off so that unit 5 will not be responsible for heating and cooling the laundry room.
4.1 LAUNDRY ROOM
Picture 1
Picture 2
Picture 3
Comments: MISCELLANEOUS INFORMATION, (REFER TO REPORT PICTURES)
1,2,3-The laundry room outlets tested are properly grounded, however the outlet above the small table is within six feet of the wash tub sink and is NOT GFCI protected. Recommend this one outlet be upgraded with GFCI protection by a licensed electrical contractor. (safety)

LAUNDRY STORAGE ROOM


 



Inspection Items
5.0 LAUNDRY STORAGE ROOM
Picture 1
Picture 2
Picture 3
Picture 4
Comments: FOR YOUR INFORMATION
1,2-There are a total of two separate water heaters located within the laundry room storage room. One is a 40 gallon for the small upstairs one bedroom unit 5 that is mounted on a separate shelf while the other is a 120 gallon for the laundry room washing machines. Recommend removing stored items that are blocking water heater access.

3,4-Laundry room also has an electrical panel which controls power for the laundry room lights, washers, and dryers, hallway lights, and storage room electric water heater.

MAINTENANCE ROOM


 



Inspection Items
6.0 MAINTENANCE ROOM
Comments: FOR YOUR INFORMATION
There is some evidence of prior moisture discolored plasterboard along both sides of the entry door plasterboard walls. They were dry to the touch at the time of inspection. This may be related to the leak in the second floor center exit stairwell that appears to have been repaired.
6.1 MAINTENANCE ROOM
Comments: FOR YOUR INFORMATION
1
6.2 MAINTENANCE ROOM
Comments: FOR YOUR INFORMATION
1-The fire alarm controller is located in the maintenance room. Central fire alarm systems are beyond the scope of the inspection.
6.3 MAINTENANCE ROOM
Comments: FOR YOUR INFORMATION
1-Complimentary view. This is basically a building maintenance work room and storage room for miscellaneous parts and is located beside the laundry room. There is a minor hole that has been made in the upper right side wall. Unknown?
6.4 MAINTENANCE ROOM
Comments: MINOR REPAIRS, (REFER TO REPORT PICTURES)
1-The maintenance room door does not solidly closed or lock. This room has a panel where keys can be accessed to each unit where repairs and robust locking of this room is recommended.

OTHER ITEMS:
-The management has a key to unlock all units except Unit 1. This unit was able to be accessed after the tenants came home for the evening. Recommend a key to Unit 1 be made and placed with rest of unit keys.

UNIT 1


 



Inspection Items
7.0 UNIT 1
Picture 1
Picture 2
Picture 3
Picture 4
Picture 5
Picture 6
Picture 7
Picture 8
Picture 9
Picture 10
Picture 11
Picture 12
Picture 13
Picture 14
Picture 15
Picture 16
Comments: FOR YOUR INFORMATION
UNIT 1 PHOTOS (1 - 16)

-Located above the first floor suspended ceiling tiles is an attic that is about 7 feet high. The attic above the second floor suspended ceiling tiles is about 10 feet high. Many of the original wood members still reside and were either not removed or are still be used and have been structurally strengthened with additional wood joists. The majority of all floor and roof decking observed throughout the building was free of moisture discoloration and deterioration. Second floor attics were all fiberglass insulated. This is good!

-All heating and air units are located above the living ceiling and are suspended from the attic ceiling.

-Water piping in use throughout the building is 3/4 inch and 1/2 inch potable CPVC type.

-All water heaters are located above the half bathroom ceiling on a structurally adequate wood framed type sub-base. All water heaters had an appropriate emergency leak pan and drain line. this is good!
7.1 UNIT 1
Picture 1
Picture 2
Picture 3
Picture 4
Picture 5
Comments: MINOR REPAIRS, (REFER TO REPORT PICTURES)
1-The light switch beside the front entry door is missing a cover (safety)

2-Another layer of floor tiles has been installed in the half bathroom. Some of these tiles are missing or are loose.

3-There is a small opening beside the kitchen faucet where a vegetable spray wand or snap-in plug/cover is recommended.

4-The upper bathroom floor tiles are deteriorated along the entry door.

5-The light switch in the upper rear bedroom is missing a cover. (safety)

OTHER ITEMS:
-The oven handle is loose.
-The metal suspended ceiling squares are rusty where painting is recommended.
-The upper bathroom sink drains slow where repairs are recommended which may include but are not limited to the use of a liquid drain cleaner or removal of drain piping for cleaning.
-The half bathroom commode tank water stays running.
-The upper bathroom commode does not flush sometimes because the tank does not always fill with water after flushed.
-The air conditioner measure temperature drop between the supply and return vents was only 8 degrees and NOT within the normal 14 to 25 degree range. System service and repairs by a licensed heat and air contractor is recommended.

UNIT 2


 



Inspection Items
8.0 UNIT 2
Picture 1
Picture 2
Picture 3
Picture 4
Picture 5
Picture 6
Picture 7
Picture 8
Picture 9
Picture 10
Picture 11
Picture 12
Picture 13
Picture 14
Picture 15
Picture 16
Picture 17
Picture 18
Picture 19
Picture 20
Picture 21
Picture 22
Picture 23
Picture 24
Comments: FOR YOUR INFORMATION
UNIT 2 PHOTOS (1 - 24)

Each sink basin was filled and then allowed to drain in order to inspect the drain piping for leakage.
8.1 UNIT 2
Comments: MINOR REPAIRS, (REFER TO REPORT PICTURES)
1-The carpet is loose at the upper bathroom threshold entry.

OTHER ITEMS:
-One set of upper bedroom bi-fold closet doors is missing.
-The lower section of the second floor stairway wood banister is loose.
-The kitchen sink aerator is aged and sprays water upward when water is turned on too much.
-The dishwasher makes loud noises occasionally. The motor may be going bad where further investigation and repair by a licensed contractor is recommended.

UNIT 3


 



Inspection Items
9.0 UNIT 3
Picture 1
Picture 2
Picture 3
Picture 4
Picture 5
Comments: FOR YOUR INFORMATION
1,2,3,4,5-Each of the 14 units has some degree of staining on the suspended ceiling tiles in the living room and dining room on the main level and in some of the bedrooms on the upper level. Some of the tiles were removed and the wood members have some staining, however still appear structurally adequate. No actual leakage was observed where all areas appeared dry. All tenants were questioned and said no leakage areas were known and that the discolored tiles were present when they moved in indicating prior and since repaired leakage.

The dining rooms tile discolorations are from previous upper level bathroom leakage, while the living room leakage is most likely from previous air conditioning condensate leakage. One tenant reported that the PVC drain line had popped out of the emergency drain pan which caused some leakage however was secured back in place and caulked.

Most likely any upstairs leaks came from previous roof leakage.

ACE Home Inspections, LLC is not responsible for any leakage within the attic that may be uncovered during a future storm because it was not raining at time of the attic inspection and only readily accessible areas are inspected and any conclusions are based solely on only what was inspected.


9.1 UNIT 3
Picture 1
Picture 2
Picture 3
Picture 4
Picture 5
Picture 6
Picture 7
Picture 8
Picture 9
Picture 10
Picture 11
Picture 12
Picture 13
Picture 14
Picture 15
Picture 16
Picture 17
Picture 18
Picture 19
Picture 20
Comments: FOR YOUR INFORMATION
UNIT 3 PHOTOS (1 - 20)

Not all areas could be inspected throughout the building due to owner stored items.
9.2 UNIT 3
Picture 1
Picture 2
Picture 3
Picture 4
Picture 5
Comments: MINOR REPAIRS, (REFER TO REPORT PICTURES)
1-One upper kitchen cabinet door has been removed.

2-The 4 top elements were not turned on because of owner items.

3-The cabinet door under the kitchen sink is off the hinges.

4-The floor tiles in the kitchen are in place, however some have some gaps between them. (cosmetic)

5-Recommend caulking where tub meets the floor.

OTHER ITEMS:
-The garbage disposal does not operate.
-The half bathroom pedestal sink is loose where it mounts to the wall.
-The living room coat closet door is difficult to operate.
-The lower section of the second floor stairway wood banister is loose.

UNIT 4


 



Inspection Items
10.0 UNIT 4
Picture 1
Picture 2
Picture 3
Picture 4
Picture 5
Picture 6
Picture 7
Picture 8
Picture 9
Picture 10
Picture 11
Picture 12
Picture 13
Picture 14
Comments: FOR YOUR INFORMATION
UNIT 4 PHOTOS (1 - 14)
10.1 UNIT 4
Picture 1
Picture 2
Picture 3
Picture 4
Picture 5
Picture 6
Picture 7
Comments: MINOR REPAIRS, (REFER TO REPORT PICTURES)
1-An 18 inch section of formica has come loose behind the kitchen sink faucet.

2-The front right stove element does not turn on.

3-The half bathroom exhaust fan vent hose to the exterior is missing.

4-The tub faucet has a constant water drip.

5-The caulking behind the upper bathroom wall sink is aged.

6-Wiring and wire-nuts are hanging loose below the light fixture over the kitchen sink.

7-The half bathroom GFCI type outlet no longer trips or resets where repairs are recommended.

OTHER ITEMS:
-The garbage disposal does not operate.
-Some walls and doors need to be painted.

UNIT 5


 



Inspection Items
11.0 UNIT 5
Picture 1
Picture 2
Picture 3
Picture 4
Picture 5
Picture 6
Picture 7
Picture 8
Picture 9
Picture 10
Picture 11
Picture 12
Comments: FOR YOUR INFORMATION
UNIT 5 PHOTOS (1 - 12)
11.1 UNIT 5
Comments: MINOR REPAIRS, (REFER TO REPORT PICTURES)
1-The floor coverings are very dirty. (cosmetic)

OTHER ITEMS:
-The vinyl flooring in the bathroom is curled up along the base of the tub.
-The oven element would not turn on.
-The bathroom exhaust fan does not operate.

UNIT 6


 



Inspection Items
12.0 UNIT 6
Picture 1
Picture 2
Picture 3
Picture 4
Picture 5
Picture 6
Picture 7
Picture 8
Picture 9
Picture 10
Picture 11
Picture 12
Picture 13
Picture 14
Comments: FOR YOUR INFORMATION
UNIT 6 PHOTOS (1 - 14)

12.1 UNIT 6
Comments: MINOR REPAIRS, (REFER TO REPORT PICTURES)
1-The carpets are dirty.

OTHER ITEMS:
-The oven handle is loose.
-The half bathroom sink stopper needs repairs.
-The half bathroom towel rod is loose.
-The kitchen flooring has some stains.
-The tub faucet has a constant water drip.
-The lower section of the second floor stairway wood banister is loose.
-The sink stopper in the upper bathroom needs repairs.
-The garbage disposal does not operate.

UNIT 7


 



Inspection Items
13.0 UNIT 7
Picture 1
Picture 2
Picture 3
Picture 4
Picture 5
Picture 6
Picture 7
Picture 8
Picture 9
Picture 10
Picture 11
Picture 12
Picture 13
Picture 14
Picture 15
Comments: FOR YOUR INFORMATION
UNIT 7 PHOTOS (1 - 15)
13.1 UNIT 7
Picture 1
Picture 2
Picture 3
Picture 4
Picture 5
Picture 6
Comments: MINOR REPAIRS, (REFER TO REPORT PICTURES)
1-An area of dining wall has been patched with wallboard compound, however needs sanded and painted. (cosmetic)

2-A small hole in the living room wall needs patched.

3-An area of floor tiles under the upper bathroom wall sink are deteriorated.

4-The carpet is loose at the upper bathroom entry.

5-An 18 inch section of formica has come loose behind the kitchen sink faucet.

6-The dining room ceiling mounted smoke alarm is missing.

OTHER ITEMS:
-The carpets are dirty.
-The upper bathroom sink stopper needs repairs.
-The air conditioner measure temperature drop between the supply and return vents was only 0 degrees and NOT within the normal 14 to 25 degree range. System service and repairs by a licensed heat and air contractor is recommended.

UNIT 8


 



Inspection Items
14.0 UNIT 8
Picture 1
Picture 2
Picture 3
Picture 4
Picture 5
Picture 6
Picture 7
Picture 8
Picture 9
Picture 10
Picture 11
Picture 12
Comments: FOR YOUR INFORMATION
UNIT 8 PHOTOS (1 -12)
14.1 UNIT 8
Comments: MINOR REPAIRS, (REFER TO REPORT PICTURES)
OTHER ITEMS:
-The dining room ceiling mounted smoke alarm is missing.
-The garbage disposal does not operate.
-There are 2 small chipped areas out of the countertop above the dishwasher,
-The toilet [paper holder is loose.
-The upper bathroom sink stopper needs repairs.
-The tub has a constant water drip.
-The front entry door knob is aged where replacement is recommended.
-The thermostat is severely loose and hanging crooked where it mounts to the wall.
-The air conditioner measure temperature drop between the supply and return vents was only 10 degrees and NOT within the normal 14 to 25 degree range. System service and repairs by a licensed heat and air contractor is recommended.

UNIT 9


 



Inspection Items
15.0 UNIT 9
Picture 1
Picture 2
Picture 3
Picture 4
Picture 5
Picture 6
Picture 7
Picture 8
Picture 9
Picture 10
Picture 11
Picture 12
Picture 13
Picture 14
Picture 15
Picture 16
Comments: FOR YOUR INFORMATION
UNIT 9 PHOTOS (1 - 16)
15.1 UNIT 9
Comments: MINOR REPAIRS, (REFER TO REPORT PICTURES)
OTHER ITEMS:
-The oven handle is loose.
-There is a small patched area of wall beside the living room closet door where sanding and painting is recommended. (cosmetic)
-The half bathroom pedestal sink is loose where it mounts to the wall.
-The heat pump electric coil emergency heat measured only 78 degrees where further investigation by a licensed heat and air contractor is recommended,
-One side of the bi-fold closet doors in the rear bedroom have been removed and placed in the hallway.

UNIT 10


 



Inspection Items
16.0 UNIT 10
Picture 1
Picture 2
Picture 3
Picture 4
Picture 5
Picture 6
Picture 7
Picture 8
Picture 9
Picture 10
Picture 11
Picture 12
Picture 13
Picture 14
Picture 15
Comments: FOR YOUR INFORMATION
UNIT 10 PHOTOS (1 - 15)
16.1 UNIT 10
Comments: MINOR REPAIRS, (REFER TO REPORT PICTURES)
1-The bottom refrigerator door seal has come loose and sticks to the bottom of the refrigerator casing. This sticking is noticed when the door is opened or closed. The area of metal behind the seal has become very corroded. Tenant states hastily repairs were previously made by trying to glue seal on and paint bottom of door where seal now sticks to paint.

OTHER ITEMS:
-The oven handle is loose.
-The deadbolt for the second floor entry door does not fully engage because the hole in the door frame is not deep enough.
-The upper bathroom sink stopper needs repairs.

UNIT 11


 



Inspection Items
17.0 UNIT 11
Picture 1
Picture 2
Picture 3
Picture 4
Picture 5
Picture 6
Picture 7
Picture 8
Picture 9
Picture 10
Picture 11
Comments: FOR YOUR INFORMATION
UNIT 11 PHOTOS (1 - 11)
17.1 UNIT 11
Picture 1
Picture 2
Picture 3
Picture 4
Picture 5
Picture 6
Comments: MINOR REPAIRS, (REFER TO REPORT PICTURES)
1-The top part of the left cabinet door under the sink is missing leaving a noticeable gap.

2-The half bathroom pedestal sink has a sizeable water leak on the drain piping where water was observed on the floor.

3-There are a couple small gouges on the living room wall.

4-A 16 inch circular area of carpet at the front entry door at the bottom of stairs is ripped and snagged.

OTHER ITEMS:
-The light over the kitchen sink does not turn on.
-The tub has a constant water drip.

UNIT 12


 



Inspection Items
18.0 UNIT 12
Picture 1
Picture 2
Picture 3
Picture 4
Picture 5
Picture 6
Picture 7
Picture 8
Picture 9
Picture 10
Picture 11
Picture 12
Picture 13
Picture 14
Comments: FOR YOUR INFORMATION
UNIT 12 PHOTOS (1 -14)
18.1 UNIT 12
Picture 1
Picture 2
Picture 3
Picture 4
Comments: MINOR REPAIRS, (REFER TO REPORT PICTURES)
1-The right rear stove element does not turn on.

2-A section of plasterboard wall in the closet under the stairs has been cut for some reason.

3-The electrical panel cover could not be opened or removed because a large expensive and heavy wall picture light and a large 40 gallon lower fish tank are blocking it.

4-The GFCI type outlet in the upper bathroom has no power because it will no longer reset where replacement is recommended by a licensed electrical contractor.

OTHER ITEMS:
-The garbage disposal does not operate.
-The floor tiles in the kitchen are aged, but functional. (cosmetic)
-The carpets are dirty.
-The interior side of the front entry door needs painted.
-The tub has a constant water drip.

UNIT 13


 



Inspection Items
19.0 UNIT 13
Picture 1
Picture 2
Picture 3
Picture 4
Picture 5
Picture 6
Picture 7
Picture 8
Picture 9
Picture 10
Comments: FOR YOUR INFORMATION
1,2,3,4,5,6,7,8,9,10-There are some moisture discolored drop ceiling tiles located above the upstairs tub. They were removed and the attic above was investigated. There was some moisture discoloration on some of the roof decking boards and around one white plumbing vent. The areas appeared dry at time of inspection. All wood roof decking was relatively free of deterioration and still appeared structurally adequate.
19.1 UNIT 13
Comments: FOR YOUR INFORMATION
Each upper hallway suspended ceiling has what appears to be an air exhaust fan device and beyond the scope of the inspection.
19.2 UNIT 13
Picture 1
Picture 2
Picture 3
Picture 4
Picture 5
Picture 6
Picture 7
Picture 8
Picture 9
Picture 10
Picture 11
Picture 12
Picture 13
Picture 14
Comments: FOR YOUR INFORMATION
UNIT 13 PHOTOS (1 -14)
19.3 UNIT 13
Comments: MINOR REPAIRS, (REFER TO REPORT PICTURES)
OTHER ITEMS:
-The thermostat is loose where it mounts to the wall.
-The carpet is dirty.
-The pedestal sink is loose where it mounts to the wall.
-The lower dining room double pane fixed window has some minor fogging along the bottom edges and the surrounding wall enclosure needs painted.
-One side of the upper bathroom toilet tissue holder is missing.
-The upper bathroom towel rod is loose.
-The upper bathroom wall sink is loose.
-The tub has a constant water drip.

UNIT 14


 



Inspection Items
20.0 UNIT 14
Picture 1
Picture 2
Picture 3
Picture 4
Picture 5
Picture 6
Picture 7
Picture 8
Picture 9
Comments: FOR YOUR INFORMATION
1,2,3,4,5,6,7,8,9-There was some moisture discoloration on some of the roof decking boards. The areas appeared dry at time of inspection. All wood roof decking was relatively free of deterioration and still appeared structurally adequate.



20.1 UNIT 14
Picture 1
Picture 2
Picture 3
Picture 4
Picture 5
Picture 6
Picture 7
Picture 8
Picture 9
Picture 10
Picture 11
Picture 12
Picture 13
Comments: FOR YOUR INFORMATION
UNIT 14 PHOTOS (1 -13)
20.2 UNIT 14
Picture 1
Picture 2
Picture 3
Comments: MINOR REPAIRS, (REFER TO REPORT PICTURES)
1-Water heater has had covers removed. Replacement is recommended both for safety and efficiency reasons. (safety issue)

2-The upper bedroom double pane fixed windows have some minor fogging along the bottom edges and the surrounding wall enclosure needs painted.

3-The tub floor is stained where heavy cleaning will be required.

OTHER ITEMS:
-The thermostat is loose where it mounts to the wall.
-The dishwasher is loose and needs to be secured to the countertop.
-The oven handle is loose.
-The carpet along the upper bathroom entry is loose and frayed.

ITEMS INSPECTED AND STYLES IN EACH AREA FOLLOWS


 



Inspection Items

WALKWAYS, DRIVEWAYS, LANDSCAPING, RETAINING WALLS

Styles & Materials
WALKWAYS:
CONCRETE
PUBLIC SIDEWALKS
DRIVEWAYS:
PUBLIC STREETS
RETAINING WALLS:
NONE
LANDSCAPING:
LEVEL PROPERTY
LANDSCAPING:
BUILDING ON CITY STREET
LANDSCAPING:
NO TREES OR SHRUBS



Inspection Items
22.0 WALKWAYS, DRIVEWAYS, PATIOS, LANDSCAPING, RETAINING WALLS (Visible condition. Checking for proper water runoff away from the house, the landscape for presence of holes, sunken areas, bald spots, eroding areas, and tripping hazards, trees and vegetation clearances, and drainage weep holes or drains at the base of retaining walls.)
Comments: INSPECTED

REAR PORCH

Styles & Materials
FOUNDATION:
CONCRETE SLAB
ROOF INFO:
NONE
COLUMNS:
NONE
FLOOR:
CONCRETE
PORCH/PATIO INFO:
REAR FIRST FLOOR EXIT DOOR
PORCH/PATIO INFO:
ACCESSED BY STEPS
PORCH/PATIO INFO:
STAIRWELL TO SECOND FLOOR



Inspection Items
23.0 ROOF, EAVES, GUTTERS, ATTIC, VENTILATION, COLUMNS, FOUNDATION, FLOOR, COVERINGS, STORAGE CLOSETS (Visible condition.)
Comments: INSPECTED
23.1 STORAGE CLOSET DOORS, LIGHTS, SWITCHES, OUTLETS (Visible condition and operation.)
Comments: INSPECTED

STEPS, STAIRS, RAILINGS, BANISTERS

Styles & Materials
EXTERIOR STEPS:
CONCRETE REAR PORCH STEPS
EXTERIOR STAIRWAYS:
REAR METAL WITH LANDING
EXTERIOR BANISTERS/RAILINGS:
METAL RAILING AND PICKETS
INTERIOR STEPS:
NONE
INTERIOR STAIRWAYS:
CARPETED CENTER STAIRWELL
INTERIOR BANISTERS/RAILINGS:
HAND-RAILS
INTERIOR STAIRWAY INFO:
EMERGENCY LIGHT
CEILING LIGHT



Inspection Items
24.0 STOOPS, STEPS, STAIRS, BANISTERS, AND RAILINGS (Visible condition. Checking for potential tripping hazards from variations in step riser heights, narrow tread steps, unlevel steps or steep stairs. Checking for adequate headroom.)
Comments: INSPECTED
24.1 SPACINGS BETWEEN ANY TWO RAILING BANISTERS OF 4 TO 5 INCHES OR LESS (Safety issue for children.)
Comments: INSPECTED

EXTERIOR SIDING, FOUNDATION EXTERIOR

Styles & Materials
SIDING MATERIAL:
BRICK SIDES AND REAR
FULL E.I.F.S. FRONT
SIDING STYLE:
BRICK
GUTTER MATERIAL:
NO GUTTERS PRESENT
FOUNDATION MATERIAL:
POURED CONCRETE
SOFFIT/FASCIA MATERIAL:
ALUMINUM



Inspection Items
25.0 FOUNDATION WALLS AND MORTAR JOINTS (Visible condition, checking for cracked, crumbled, loose, missing, eroded areas, or large gaps)
Comments: INSPECTED
25.1 EXTERIOR WALL COVERINGS, FLASHING,TRIM, AND CAULKING (Visible condition. A wall flashing is defined as a material used around angles or junctions on exterior walls to prevent water leakage.)
Comments: INSPECTED
25.2 HOUSE FRAMING (Visible condition, checking for any cracks developing outside of the house, cracks between a chimney and the exterior wall or any cracks running outward at an angle from the upper corners of windows and door frames.)
Comments: INSPECTED
25.3 OUTSIDE ACCESS TO HOUSE IS RODENT PROOF
Comments: INSPECTED

DOORS, WINDOWS, SHUTTERS, AWNINGS

Styles & Materials
EXTERIOR ENTRY DOORS:
4 TOTAL EXTERIOR DOORS
EXTERIOR ENTRY DOORS:
FRONT-METAL/FULL GLASS
OTHERS-FULL METAL
EXTERIOR ENTRY DOORS:
FRONT-INTERIOR ENTRY DOOR
INTERIOR DOORS:
WOOD/HOLLOW/FLUSH
HOUSE WINDOWS:
WOOD
HOUSE WINDOW TYPE:
FIXED
HOUSE WINDOW COMPANY:
UNKNOWN
HOUSE WINDOW DATE:
UNKNOWN
HOUSE WINDOW INFO:
11 BUILDING FIXED WINDOWS



Inspection Items
26.0 WINDOWS, SHUTTERS AND AWNINGS (Visible condition and checking for the presence and functionality of window flashing and operation of windows and window locks.)
Comments: INSPECTED
26.1 ENTRY DOORS, STORM DOORS, SECURITY DOORS, AND DOORBELL (Visible condition and operation, checking hardware, locks, coverings, frame, trim, weatherstripping, presence of deadbolts on all exterior doors, proper locking, opening, and closing of sliding glass doors, and the presence of a security dead-pin in all sliding glass doors.)
Comments: INSPECTED

GUTTERS, EAVES, CHIMNEY, ROOF EXTERIOR

Styles & Materials
VIEWED ROOF FROM:
WALKED ROOF
ROOF TYPE:
FLAT
ROOF COVERING:
MODIFIED BITUMEN
LAYERS:
ONE
ESTIMATED ROOF AGE:
5 TO 10 YEARS
ROOF VENTILATION:
ROOF VENTS
ROOF VENTILATION:
SIDE BRICK VENTING
ROOF PENETRATIONS:
29 TOTAL ROOF PENETRATIONS
PENETRATION BREAKDOWN:
10 WHITE PLUMBING VENTS
6 CENTER ROOF DRAINS
1 ENTRY SCUTTLE HOLE
8 A/C UNIT LINE OPENINGS
4 AIR EXHAUST VENTS



Inspection Items
27.0 ROOF COVERING (Visible condition. Checking roof penetrations such as, roof vents, ridge vents, wind turbines, soffit vents, gable vents, chimneys, furnace flues, water heater flues, plumbing vents, skylights and any other penetrations. Checking flashings which are used to seal around roof penetrations and intersections. Checking rain caps on chimneys and flues.)
Comments: INSPECTED
27.1 SOFFIT, FASCIA, EAVES, GUTTERS, DOWNSPOUTS (Visible condition. Checking if gutters are provided where necessary, including porches, flat roofs, and dormers. Checking whether splasblocks are in place if underground piping is not used for rain gutter drainage.)
Comments: INSPECTED

ATTIC, ROOF INTERIOR (first and second floor)

Styles & Materials
ROOF STRUCTURE:
2 X 12 WOOD RAFTERS
PLYWOOD ROOF DECKING
CEILING STRUCTURE:
2x6 WOOD JOISTS
INSULATION TYPE:
BATT
INSULATION INCHES:
6 INCHES
R- VALUE:
R-19 OR BETTER
ACCESS LOCATED IN:
HALLWAY
RAFTER SPACING:
16 INCHES
JOIST SPACING:
16 INCHES



Inspection Items
28.0 ATTIC, ROOF INTERIOR (Visible condition. Checking attic insulation, exposed wiring, lights and water pipes. Checking to see that all attic areas are accessible, all exposed sections of chimney in attic are free of soot and creosote leakage, that soffit vents are not covered with insulation, and attic ventilation vent screening which keeps animals out)
Comments: INSPECTED
28.1 GAS FLUE AND CHIMNEY FIRESTOPPING (Visible condition. Firestopping refers to size of the hole made in the ceiling and roof so as to maintain the proper clearance from a hot metal flue pipe or chimney brick.)
Comments: INSPECTED
28.2 DO ALL FLUES AND VENTS PRESENT IN ATTIC TERMINATE TO THE EXTERIOR (Water heater flue, furnace flue, metal chimney flue, plumbing vents, bathroom fan vents, range hood vent, dryer vent, etc...)
Comments: INSPECTED
28.3 RAFTERS, DECKING, JOISTS OR TRUSSES (Visible condition. Check for rafters pulling away from ridge board, rot, cracks, splits, cut, altered or missing supports.)
Comments: INSPECTED
28.4 IS ATTIC FREE OF VISIBLE ROOF LEAKS OR DETERIORATION (Flashing refers to materials, usually metal, that join parts of the house to the roof. Common places where roof leaks occur are flashings around chimneys, metal gas flues, plumbing vents, turbines, dormers, valleys, or any other roof penetrations or intersections.)
Comments: INSPECTED
28.5 IS ATTIC FREE OF VISIBLE CONDENSATION OR MOISTURE DAMAGE DUE TO IMPROPER VENTILATION (Often what appears to be a leak is in fact condensation, and a sign of inadequate ventilation. Proper attic ventilation reduces heat in summer and prevents condensation in winter. It allows air to carry off water vapor before it can condense and cause moisture damage.)
Comments: INSPECTED
28.6 INSTALLED MECHANICAL VENTILATION SYSTEMS (Visible condition and operation of power ventilators and fans)
Comments: INSPECTED

KITCHEN, APPLIANCES

Styles & Materials
KITCHEN INFO:
CEILING LIGHT
CEILING MATERIAL:
SUSPENDED CEILING TILES
WALL MATERIAL:
PLASTERBOARD
FLOOR COVERING:
FLOOR TILES
CABINETRY:
WOOD AND PRESSED WOOD
CABINETRY:
PRE-FAB TYPE
COUNTERTOP:
FORMICA
SINK:
STAINLESS/DUAL BASIN
WATER CONNECTION:
COPPER TUBING
DRAIN PLUMBING:
WHITE PVC(polyvinyl chloride) PIPING
APPLIANCE COLOR SCHEME:
WHITE
REFRIGERATOR:
HOTPOINT
DISPOSER:
BADGER
DISHWASHER:
HOTPOINT
TRASH COMPACTORS:
NONE
BUILT-IN MICROWAVE:
NONE
RANGE HOOD:
AIRCARE
HOOD EXHAUST:
RECYCLED EXHAUST
RANGE/COOKTOP BRAND:
HOTPOINT
RANGE/COOKTOP ENERGY:
ELECTRIC
ELEMENT/BURNER:
COIL ELEMENT
OVEN ENERGY:
ELECTRIC



Inspection Items
29.0 KITCHEN (Visible condition of ceiling, walls, cabinets, shelving, countertops, plumbing. Checking that all outlets within six feet of sink have GFCI protection, and there are separate water shut-off valves for faucet, dishwasher, and ice-maker.)
Comments: INSPECTED
29.1 KITCHEN (Visible condition and operation of windows, doors, floor, cabinet doors, drawers, lights, switches, outlets, sink, faucet, spray nozzle and all appliances staying with house: range, oven, microwave, vent hood, dishwasher, disposal, refrigerator or any other appliances. Checking that sink and dishwasher drain properly, and hot and cold water pressure, volume, and temperature are adequate.)
Comments: INSPECTED
29.2 RANGE HOOD VENTING SYSTEM (If range hood is nonvented type, is there a clean charcoal or aluminum filter in place. A nonvented hood is for filtering odors and grease vapors and will not remove heat or steam like a vented range hood. A non-vented range hood is identified by louvers on the front of the hood and does not vent to exterior as a vented hood does.)
Comments: INSPECTED
29.3 ARE FAUCETS FREE OF HAMMERING AND VIBRATING NOISES WHEN TURNED ON/OFF RAPIDLY (This occurs when water flowing in the pipe comes to an abrupt stop, introducing shock and vibrations that can damage pipes or fittings. It is caused by improper sized pipes and can be fixed with an air chamber or antiknock coil which provides an air cushion to absorb shock.)
Comments: INSPECTED
29.4 DOES SINK DRAIN INTO A P-TRAP UNDER THE SINK (A trap is needed to provide a water seal that blocks sewer gases from seeping back into house. Some homes still have S-type traps that do not always vent properly. If a sucking and gurgling noise occurs after almost all the water has drained, the water seal has been lost. All S-traps should be converted to P-traps.)
Comments: INSPECTED
29.5 DOES SINK HAVE AN AIR GAP TO PREVENT BACK SIPHONAGE (Simply speaking, the air gap prevents the dirty sink water from being sucked back into the clean water supply pipes through the end of the faucet if the sink should overflow. There should be a gap of at least 1 inch between the end of the faucet where the water exits and the flood rim of the sink.)
Comments: INSPECTED

INTERIOR ROOMS (dining room, living room, hallway, front bedroom, rear bedroom)

Styles & Materials
CEILING MATERIAL:
SUSPENDED CEILING TILES
WALL MATERIAL:
PLASTERBOARD
FLOOR MATERIAL:
ALL ARE CARPET EXCEPT SOME
DINING ROOMS ARE FLOOR TILES
OR VINYL FLOOR COVERING
ROOM INFO:
LIVING ROOM HAS HALF BATH
LIVING ROOM HAS CEILING LIGHT
LIVING ROOM HAS COAT CLOSET
LIVING ROOM HAS STORAGE CLOSET
LIVING ROOM HAS SMOKE ALARM
LIVING ROOM HAS THERMOSTAT
ROOM INFO:
HALLWAY HAS SMOKE ALARM
HALLWAY HAS FULL BATH
SOME HALLWAYS HAVE EXIT DOOR
SOME BEDROOMS HAVE EXIT DOOR
BEDROOMS HAVE CLOSET
ROOM INFO:
DINING ROOM HAS ELECTRIC PANEL
DINING ROOM OPEN BESIDE KITCHEN



Inspection Items
30.0.A CEILING AND WALLS (Visible condition.)
Comments: INSPECTED
30.1.A WINDOWS, DOORS, FLOOR, LIGHTS, SWITCHES, OUTLETS (Visible condition and operation.)
Comments: INSPECTED

MAINTENANCE ROOM

Styles & Materials
CEILING MATERIAL:
PLASTERBOARD
WALL MATERIAL:
PLASTERBOARD
FLOOR MATERIAL:
FLOOR TILES
ROOM INFO:
SHELVING



Inspection Items
30.0.B CEILING AND WALLS (Visible condition.)
Comments: INSPECTED
30.1.B WINDOWS, DOORS, FLOOR, LIGHTS, SWITCHES, OUTLETS (Visible condition and operation.)
Comments: INSPECTED

LAUNDRY ROOM

Styles & Materials
CEILING MATERIAL:
SUSPENDED CEILING TILES
WALL MATERIAL:
PLASTERBOARD
FLOOR MATERIAL:
FLOOR TILES
ROOM INFO:
3 GE WASHERS
2 GE DRYERS
ROOM INFO:
FLOURESCENT LIGHTING
PLASTIC WASH SINK
ROOM INFO:
ATTIC ENTRY HATCH
STORAGE CLOSET



Inspection Items
30.0.C CEILING AND WALLS (Visible condition.)
Comments: INSPECTED
30.1.C WINDOWS, DOORS, FLOOR, LIGHTS, SWITCHES, OUTLETS (Visible condition and operation.)
Comments: INSPECTED

LAUNDRY ROOM STORAGE CLOSET

Styles & Materials
CEILING MATERIAL:
PLASTERBOARD
WALL MATERIAL:
PLASTERBOARD
FLOOR MATERIAL:
FLOOR TILES
ROOM INFO:
2 WATER HEATERS
ROOM INFO:
ELECTRIC PANEL
ROOM INFO:
SHELVING



Inspection Items
30.0.D CEILING AND WALLS (Visible condition.)
Comments: INSPECTED
30.1.D WINDOWS, DOORS, FLOOR, LIGHTS, SWITCHES, OUTLETS (Visible condition and operation.)
Comments: INSPECTED

COMMON BUILDING LOWER HALLWAY

Styles & Materials
CEILING MATERIAL:
PLASTERBOARD
WALL MATERIAL:
PLASTERBOARD
FLOOR MATERIAL:
CARPET
ROOM INFO:
DOUBLE DOOR FRONT ENTRY
REAR ENTRY DOOR
LAUNDRY ROOM
ROOM INFO:
3 EMERGENCY LIGHTS
3 SMOKE ALARMS
2 ATTIC SCUTTLE HATCHES
ROOM INFO:
2 FIRE EXTINGUISHERS
EACH UNIT AS ENTRY DOOR
MAINTENANCE ROOM ACCESS



Inspection Items
30.0.E CEILING AND WALLS (Visible condition.)
Comments: INSPECTED
30.1.E WINDOWS, DOORS, FLOOR, LIGHTS, SWITCHES, OUTLETS (Visible condition and operation.)
Comments: INSPECTED

COMMON BUILDING UPPER HALLWAY

Styles & Materials
CEILING MATERIAL:
PLASTERBOARD
WALL MATERIAL:
PLASTERBOARD
FLOOR MATERIAL:
CARPET
ROOM INFO:
REAR ENTRY DOOR
CENTER EXIT STAIRWELL
EACH UNIT HAS ENTRY DOOR
ROOM INFO:
3 EMERGENCY LIGHTS
3 SMOKE ALARMS
2 ATTIC SCUTTLE HATCHES
ROOM INFO:
2 FIRE EXTINGUISHERS



Inspection Items
30.0.F CEILING AND WALLS (Visible condition.)
Comments: INSPECTED
30.1.F WINDOWS, DOORS, FLOOR, LIGHTS, SWITCHES, OUTLETS (Visible condition and operation.)
Comments: INSPECTED

BATHROOMS (hallway full bath, living room half bath)

Styles & Materials
CEILING MATERIAL:
SUSPENDED CEILING TILES
WALL MATERIAL:
PLASTERBOARD
FLOOR COVERING:
FLOOR TILES OR VINYL
DRAIN PIPING UNDER SINKS:
WHITE PVC(polyvinyl chloride) PIPING
SINK WATER SUPPLY CONNECTION:
GRAY PLASTIC TUBING
BATHROOM INFO:
FULL-1 TUB WITH SHOWER
FULL-MOST HAVE WALL SINKS
FULL-SOME HAVE SMALL VANITY
BATHROOM INFO:
BOTH HAVE 1 EXHAUST FAN
BOTH HAVE A WALL LIGHT
BATHROOM INFO:
FULL-OPEN TOWEL CLOSET
FULL HAS MEDICINE CABINET
ACRYLIC TUB



Inspection Items
31.0 BATHROOM (Visible condition of ceiling, walls, cabinets, countertops, and caulking.)
Comments: INSPECTED
31.1 BATHROOM (Visible condition and operation of windows, doors, floor, cabinet doors, drawers, exhaust fans, lights, switches, outlets, sinks, tubs, showers, and commodes. Checking presence of cut-off valves for faucets and commodes, proper draining of sinks, tubs, showers and commodes, use of P-traps and not old S-traps, proper air-gap for sinks, tubs, and hand-held shower wands to prevent back siphonage, faucets for improper hammering and vibrating noises when turned on/off rapidly, adequacy of hot and cold water pressure, volume, and temperature, exhaust fans for proper venting to building exterior and outlet GFCI protection.)
Comments: INSPECTED

PLUMBING (Main, Exterior, Water Heater, Washer, Dryer)

Styles & Materials
PLUMBING SUPPLY:
3/4 INCH POTABLE CPVC
DISTRIBUTION:
1/2 INCH POTABLE CPVC
PLUMBING WASTE:
PVC
WASTE SYSTEM:
PUBLIC
WATER SOURCE:
PUBLIC
WATER CUT-OFF:
AT STREET
WATER HEATER LOCATION:
CEILING ABOVE HALF BATH
WATER HEATER POWER SOURCE:
ELECTRIC
CAPACITY:
40 GALLON
MANUFACTURER:
RUUD
DRYER VENT:
METAL
DRYER POWER SOURCE:
220 ELECTRIC
WASHER DRAIN SIZE:
2" DIAMETER
WATER HEATER DATE:
UNIT 1 - 12/1992
WATER HEATER DATE:
UNIT 2 - 04/1992
WATER HEATER DATE:
UNIT 3 - 03/1993
WATER HEATER DATE:
UNIT 4 - 04/1992
WATER HEATER DATE:
UNIT 5 - 05/1992
WATER HEATER DATE:
UNIT 6 - 12/1991
WATER HEATER DATE:
UNIT 7 - 05/1992
WATER HEATER DATE:
UNIT 8 - 03/1993
WATER HEATER DATE:
UNIT 9 - 06/1992
WATER HEATER DATE:
UNIT 10 - 05/1992
WATER HEATER DATE:
UNIT 11 - 05/1992
WATER HEATER DATE:
UNIT 12 - 03/1993
WATER HEATER DATE:
UNIT 13 - 12/1992
WATER HEATER DATE:
UNIT 14 - 04/1992



Inspection Items
32.0 PLUMBING SYSTEM
Comments: FOR YOUR INFORMATION
Electric water heaters are functional and have a proper TPR valve discharge pipe. This is good! There were no potable water expansion tanks observed which are always recommended but are NOT required. (Maintenance tip.)

ADDITIONAL EXPANSION TANK INFORMATION:

A potable water expansion tank is always recommended, but not required between the cold water line and the water pressure reducing valve. It is designed to absorb thermal expansion and to maintain balanced pressure throughout the potable water supply system. Heated water expands and in a domestic hot water system the system may be closed when isolated by a pressure reducing valve. Provisions should be made for this expansion. The expansion tank absorbs the increased volume of water created when the hot water storage tank is heated and keeps the system pressure below the relief setting of the T & P relief valve. It is a pre-pressurized steel tank with an expansion membrane that prevents contact of water with the air in the tank. This prevents loss of air to the water and ensures a longer system life. The tank has a polypropylene liner, butyl diaphragm and a field adjustable pre-charge. Refer to sample picture.


Visit this web link for a general idea on how long should the components and systems in your home last.

<http://www.oldhouseweb.com/stories/Detailed/10382.shtml>
32.1 PLUMBING SYSTEM
Comments: FOR YOUR INFORMATION
1-----UPGRADE-----The simplest backflow protection is the simple air gap between the end of a sink faucet where the water exits and the flood rim of the sink as explained in the bathroom section. Another place where backflow protection is needed is on outside hose bibs or faucets. This involves purchasing a relatively inexpensive backflow preventer that easily screws on to the end of the faucet that will allow water to flow in only one direction, out of your faucet. This prevents any contaminated water in your hose from being sucked back through the house water supply. It is recommended that present hose bibs be upgraded with backflow preventers.
32.2 WATER HEATER, PTV - PRESSURE TEMPERATURE VALVE, PTV DRAIN PIPING (Visible condition. Checking presence of a drain pan under unit if installed in attic or room over a living area, and presence of a cold water inlet water cut-off valve.)
Comments: INSPECTED
32.3 ELECTRIC WATER HEATER EXTERIOR TANK WIRING AND ELEMENT COVERS (Visible condition.)
Comments: INSPECTED
32.4 EXPOSED INTERIOR WATER PIPING (Visible condition, looking for leaks, corrosion, sagging sections, and valves where it enters house and stops at the point where it enters rooms where it then will be described in each rooms description in this report.)
Comments: INSPECTED
32.5 EXTERIOR HOSE FAUCETS, WATER PRESSURE, WATER VOLUME, WATER DRAINS (Visible condition and operation. Checking for presence of faucet backflow preventers.)
Comments: NOT PRESENT
32.6 CLOTHES WASHER WATER CONNECTIONS, DRAIN PIPE, AND HOSES (Visible condition.)
Comments: INSPECTED
32.7 ELECTRIC CLOTHES DRYER OUTLET OR GAS CLOTHES DRYER CONNECTION (Visible condition. Checking dryer exhaust vent for exterior building termination and exterior cover with functional flap.)
Comments: INSPECTED

ELECTRICAL (Service, Interior Distribution Panels, Exterior)

Styles & Materials
SERVICE DROP TO HOUSE:
BELOW GROUND
SERVICE DROP TO HOUSE:
IN CONDUIT
SERVICE DROP TO HOUSE:
ATTACHES TO SIDING
MAIN POWER DISCONNECT:
NO MAIN TO CUT ALL POWER
MAIN POWER DISCONNECT:
MUST CUT OFF ALL BREAKERS
MAIN PANEL CAPACITY:
125 AMP
MAIN PANEL TYPE:
CIRCUIT BREAKERS
MAIN PANEL LOCATION:
DINING ROOM
15 AND 20 AMP CIRCUIT TYPE:
ALL COPPER
MAIN PANEL MANUFACTURER:
SQUARE D
MAIN PANEL MANUFACTURED:
UNKNOWN



Inspection Items
33.0 ELECTRICAL SYSTEM
Comments: FOR YOUR INFORMATION
The electrical panels appeared free of moisture discoloration, corrosion, and deterioration. This is good! Please see rest of electrical section for all items inspected.

Two breakers had two wires, which is allowed with this type of breaker, as stated on the breakers.

33.1 ELECTRICAL SYSTEM
Comments: FOR YOUR INFORMATION
All readily accessible outlets were tested with a SureTest electrical tester and found to be properly grounded. The kitchen and bathroom bathroom outlets are GFCI protected. This is good!

-----UPGRADE-----There were no AFCI protected bedroom outlets observed. These are NOT required, based on the age of the house, however are always recommended, as a safety upgrade. Please read general GFCI and AFCI information below.

Remember that breakers are designed to only protect the wiring, while a GFCI is designed to protect you!

GENERAL GFCI AND AFCI INFORMATION:

A GFCI or Ground-Fault-Circuit Interrupter is a device intended for the protection of personnel that functions to de-energize a circuit within an established period of time when a current to ground exceeds the values established for a Class A device. Class A ground-fault circuit interrupters trip when the current to ground has a value in the range of 4ma (milli-amps) to 6ma (milli-amps). Remember that breakers are designed to protect only the wiring and GFCI's are designed to protect people against electrical shock. It is always recommended that kitchen outlets within six feet of the sink, bathroom outlets, unfinished basement or crawlspace areas, garage, exterior, hot tubs, saunas, whirlpool tubs, or any outlets residing on or by any body of water be upgraded to GFCI type outlets by a licensed electrical contractor.

Starting January 1, 2002, The National Electrical Code, Section 210-12, requires that all branch circuits supplying 125 volts, single phase, 15 and 20 ampere outlets installed in bedrooms be protected by an arc-fault circuit interrupter. They may eventually be required elsewhere, but for now just in bedrooms because a CPSC study showed many home fire deaths were related to bedroom circuits. The AFCI - arc-fault-circuit-interrupter will shut off a circuit in a fraction of a second if arcing develops. The current inside of an arc is not always high enough to trip a regular breaker.
33.2 EXTERIOR LIGHTS, SWITCHES, OUTLETS (Visible condition and operation)
Comments: INSPECTED
33.3 SERVICE ENTRANCE CABLE (Visible condition of cable, splices, house connection, porcelain insulators, mast, masthead or gooseneck, conduit and if limbs or vines are in the way. Service is run aerially overhead or buried underground. The home owner's responsibility starts after cable splice where aerial feed is connected to the house, and for a buried feed at the meter.)
Comments: INSPECTED
33.4 METER BASE TO PANEL (Visible condition of base, how its attached to house, all cables and connectors, look for illegal wire taps running to another panel or device which could severely overload the service utility drop and meter base, and does meter base amp rating closely match the fuse or circuit breaker panel amp rating.)
Comments: INSPECTED
33.5 PANELS, FUSE BOXES, AND SUB-PANELS (Visible condition. Checking panels for proper circuit or fuse labeling, all circuit breakers same brand name as panel, one main breaker or disconnect that cuts all power to house. Check that all wires to single-pole breakers are colored black and not white.)
Comments: INSPECTED
33.6 ELECTRICAL SYSTEM GROUND (Visible condition. A ground wire bleeds stray voltages to ground and current should not flow continuously in this wire. A ground wire from the neutral/grounding bus bar in main panel runs to a grounding electrode or rod. There should also be a ground wire from the main panel neutral/grounding bus bar to metal water pipes. Water pipes should be voltage free. Check water pipes for presence of voltage.)
Comments: INSPECTED
33.7 PANEL BONDING STRAP (Visible condition. A bonding strap or panel bond, is required in every main panel to connect the neutral/grounding bus bar to the panel frame so that the metal panel can't shock you if a live wire touches it.)
Comments: INSPECTED
33.8 ARE PANEL FILLER PLATES IN PLACE WITH NONE MISSING (Filler plates are little knockouts that are removed from panel front if breakers are installed. If no breaker was installed, this open spot is where someone could reach in and touch a hot spot.)
Comments: INSPECTED
33.9 ARE LOCATIONS OF PANELS AND SUB-PANELS READILY ACCESSIBLE (A countertop or workbench directly in front of panel makes it not readily accessible. A shorter person won't be able to reach and shut-off a breaker in an emergency.)
Comments: INSPECTED
33.10 IS THERE ONLY ONE WIRE TO EACH SERVICE ENTRY CABLE LUG IN MAIN PANEL (This is where the cable from meter connects into panel. Other wires, called illegal taps, on these two lugs are left without overcurrent protection. Don't confuse an illegal tap with surge-protection wiring where two small wires feed into main lugs and go to a small lightning-surge arrestor.)
Comments: INSPECTED
33.11 IS THERE ONLY ONE WIRE TO EACH BREAKER SCREW, NEUTRAL OR GROUND BUS SCREW, OR FUSE (Multiple wires are a sign of an overloaded panel and are dangerous because the wires can work loose from vibration and become a fire hazard. There is an exception to the rule: Square D, type-QO, size 15, 20, 30 amp breakers are listed for up to two 10 gauge wires.)
Comments: INSPECTED
33.12 ARE ALL WIRES TO EACH FUSE OR CIRCUIT BREAKER SIZED PROPERLY (This occurs if undersize wire is used with oversize breakers or fuses. This is critical so that whatever load is connected to the circuit breaker will be properly protected.)
Comments: INSPECTED
33.13 ARE ALL WIRES ON 15 0R 20 AMP CIRCUITS COPPER AND NOT SINGLE STRAND ALUMINUM (Aluminum wired homes built from 1965 to 1972 have had numerous problems with electrical connections to receptacles and switches.)
Comments: INSPECTED
33.14 IS PANEL FREE OF ANY WATER DAMAGE (The signs of moisture damage are brown iron stains and white corrosion on breakers and hot tabs inside panel.)
Comments: INSPECTED
33.15 IS PANEL FREE OF ANY DETERIORATION (Visible condition looking for signs of arcing, burn marks, blistering, or discoloration. If breaker wire connection has overheated, usually because it became loose, there will be discolored or burned insulation.)
Comments: INSPECTED
33.16 ARE SUB-PANEL GROUNDS ISOLATED FROM NEUTRALS (A sub-panels most common use is to provide a secondary panel some distance from the main service panel. In any sub-panel, grounds and neutrals must be kept separate from each other.)
Comments: INSPECTED
33.17 ARE APPROPRIATE OUTLETS GFCI PROTECTED (A Ground Fault Circuit Interrupter is a safety device that senses any shock hazard and interrupts the flow of electricity in the circuit. Receptacles requiring GFCIs are bathrooms, kitchen countertops, wet bar sinks, garages, pools, spa lights, and any outdoors below 6'6".)
Comments: INSPECTED
33.18 WERE A REPRESENTATIVE NUMBER OF OUTLETS TESTED (Verify proper outlet operation with a Suretest tester that tests for proper wiring, reversed polarity, voltage drop, ground impedance, Ground-to-Neutral voltage, line voltage, high resistance grounds, and false or bootleg grounds. The tester also verifies GFCI, ground fault circuit interrupter type outlets.
Comments: INSPECTED

HEATING SYSTEM

Styles & Materials
HEAT FOR:
ALL LEVELS
LOCATION:
CEILING ABOVE LIVING ROOM
FUEL SOURCE:
ELECTRIC
HEAT TYPE:
FORCED AIR
BTU RANGE:
UNKNOWN
HEAT SYSTEM BRAND:
MOST ARE UNITARY PRODUCTS
SOME ARE GOODMAN - UNIT 8
FILTER TYPE:
DISPOSABLE
DUCTWORK:
FIBERGLASS/RECT/ROUND
MANUFACTURED:
1993
FILTER SIZE:
20x20
EMERGENCY HEAT PACK:
ELECTRIC COILS
EMERGENCY HEAT MEASURED:
UNIT 1 94
UNIT 2 96
UNIT 3 98
UNIT 4 91
UNIT 5 101
UNIT 6 94
UNIT 7 91
UNIT 8 99
UNIT 9 78
UNIT 10 101
UNIT 11 99
UNIT 12 92
UNIT 13 102
UNIT 14 93



Inspection Items
34.0 HEATING SYSTEM
Comments: FOR YOUR INFORMATION
The heat side of heat pumps located in the living room ceilings could not be operated since it was greater than 65 degrees where damage could result to system components after running the air conditioner. Annual heating system service is always recommended by a licensed heating and air contractor.
34.1 HEATING SYSTEM
Comments: FOR YOUR INFORMATION
The systems consists of a heat pump which are usually only effective down to around 35 degrees. At temperatures below 35 degrees it may become necessary to use the electric coil back-up heating system. This must be turned on manually from the thermostat.
34.2 HEATING SYSTEM
Comments: FOR YOUR INFORMATION
Visit this web link for a general idea on how long should the components and systems in your home last.

<http://www.oldhouseweb.com/stories/Detailed/10382.shtml>
34.3 CONVENTIONAL HEAT PUMP (Visible condition and operation. It is an air conditioner that contains a "reversing" valve to switch between "air conditioner" and "heater" by changing the direction of Freon flow. Simply, the warm air blowing out of the outside unit, now blows out of the inside unit to heat the home.)
Comments: INSPECTED
34.4 WAS CONVENTIONAL HEAT PUMP CYCLED ONLY IN MODE IT FOUND IN (This is important to prevent possible compressor damage. If found in the cooling mode, do not run the heat mode. If found in the heat mode, do not run the cooling mode.)
Comments: INSPECTED
34.5 ELECTRIC FURNACE (Visible condition and operation. Heat produced by electrical resistance serves as the main heating source or as auxiliary heat for heat pumps. The electric furnace does not have a heat exchanger like a gas furnace so there is not a problem with flue gases. The heat is supplied by a series of coils. Each coil has a thermal fuse and temperature limit switch.)
Comments: INSPECTED
34.6 INSTALLED HEATING EQUIPMENT (Visible condition and check presence of conditioned air source in all rooms, furnace blower free of any excess noise or vibration, and return air filter is present and clean.)
Comments: INSPECTED
34.7 WAS A TEMPERATURE MEASURED AT SUPPLY AND RETURN (Typical furnace operating temperatures are: NATURAL GAS: 130-140 degrees, OIL/PROPANE: 125-135 degrees, ELECTRIC: 110-120 degrees, HEAT PUMP: 95-100 degrees.)
Comments: INSPECTED
34.8 DISTRIBUTION SYSTEMS (Visible condition, checking fans, pumps, ducts and piping, insulation, air filters, registers, radiators, fan coil units and convectors)
Comments: INSPECTED
34.9 THERMOSTAT (Visible condition, checking if, level on wall, loose, equipment turns on/off from thermostat controls.)
Comments: INSPECTED

COOLING SYSTEM

Styles & Materials
OUTSIDE UNIT LOCATION:
FLAT ROOF
MEASURED TEMP SUPPLY/RETURN:
UNIT 1 68 76 ***
UNIT 2 58 78
UNIT 3 61 78
UNIT 4 58 77
UNIT 5 60 78
UNIT 6 61 79
UNIT 7 83 83 ***
UNIT 8 66 76 ***
UNIT 9 62 78
UNIT 10 56 76
UNIT 11 58 76
UNIT 12 61 77
UNIT 13 58 76
UNIT 14 61 76
CENTRAL AIR OUTSIDE UNIT:
UNITARY PRODUCTS
NUMBER OF TONS:
ESTIMATED 1 1/2 TONS
CENTRAL AIR UNIT:
HEAT PUMP
CENTRAL AIR OUTSIDE UNIT:
ALL 14 UNITS - 03/1993
COOLING SYSTEM INFO:
SQUARE D EXTERIOR 60 AMP
SERVICE DISCONNECT BOX
LOCATED BY ROOF UNITS
CENTRAL AIR INSIDE UNIT:
MOST ARE UNITARY PRODUCTS
SOME ARE GOODMAN - UNIT 8



Inspection Items
35.0 COOLING SYSTEM
Comments: FOR YOUR INFORMATION
All interior attic evaporator coil units have condensation water that drips down through a primary PVC pipe that runs directly out of the bottom of the coils to the exterior. There is also an emergency drain pan under each coil unit which is there to prevent any leakage from above from getting onto the house ceilings. This emergency pan is supposed to have both or at least one of the following means of overflow protection. A PVC pipe out of the side of the pan to the exterior which allows any water to drain away and/or a float switch to cut power to the unit if a high water level is obtained in the pan. It is always better to have both forms of protection, however only one or the other is required. These are are considered a back-up leak prevention system.

This buildings units emergency pans have a float switch and a PVC pipe to the exterior. This is good!
35.1 COOLING SYSTEM
Comments: FOR YOUR INFORMATION
Each unit has a central cooling systems which are sometimes referred to as a "split system" which has an exterior condenser coil unit and an interior evaporator coil unit. Annual cooling system service by a licensed heating and air contractor is always recommended. (Maintenance tip.) The condenser coil units are located on the flat roof surface.
35.2 COOLING SYSTEM
Comments: FOR YOUR INFORMATION
1-Conventional heat pumps were found in cooling mode and cycled only in cooling mode. Heating modes were not inspected. (This is important to prevent possible compressor damage. If found in the cooling mode, do not run the heat mode. If found in the heat mode, do not run the cooling mode.) Only cooling mode was inspected because outside temperature was above 65 degrees.
35.3 INSTALLED COOLING EQUIPMENT (Visible condition, checking condenser and evaporator units are free of any excess noise and vibration, condenser unit free of overgrowth, coil blockage, and sitting level on a slab.)
Comments: INSPECTED
35.4 OUTSIDE CONDENSER UNIT (Visible condition. It consists of compressor, coils, and blower fan. The compressor compresses low-pressure cold Freon gas, turning it into high pressure Freon gas that runs through the coils with the fan blowing across them to dissipate its heat, and condense into a hot Freon liquid. Warm air should be blowing when you walk by it outside.)
Comments: INSPECTED
35.5 INSIDE EVAPORATOR UNIT (Visible condition. It consists of a Freon metering device that is either an expansion valve or capillary tube, coils, and blower fan. Hot Freon liquid runs through the metering device, evaporates into cold, low-pressure Freon gas, runs through the coils that allow the gas to absorb heat and cool the house as the fan blows air through the coil and out ducts)
Comments: INSPECTED
35.6 CONDENSATION PAN AND LINES (Visible condition, checking for leaks, rust or deterioration and where the line terminates. The pan is where water extracted from the air by the evaporator runs into. Some systems use a pump to extract water out of the pan. Central air conditioning systems provide comfort cooling by lowering air temperature and removing excess moisture.)
Comments: INSPECTED
35.7 WAS TEMPERATURE DROP MEASUREMENT TAKEN FROM SUPPLY AND RETURN VENTS (A low drop could indicate low Freon charge. A high drop could indicate a dirty coil, filter or blower. There are other reasons why the temperature drop is out of range such as thermostat calibration and humidity.)
Comments: INSPECTED
35.8 IS COOLING UNIT ADEQUATE FOR SIZE OF HOUSE (The general rule of thumb is 1 ton for every 550 square feet of living space.)
Comments: INSPECTED

Prepared Using HomeGauge http://www.homegauge.com/ SHGI (c) 2000-2003 : Licensed To Jeffrey James Aiken